CERTIFIED TEST DATA
AIR PERFORMANCE CURVE
(4 In. Duct)
TYPICAL INSTALLATION |
|
| ROOF CAP |
(90°) ELBOW |
|
4" DIA. DUCT | WALL CAP |
|
|
STATIC
0.50
0.40
0.30
0.20
0.10
0.00
0 25
50 Feet
40 Feet
30 Feet
20 Feet
10 Feet
50 75 100 125
CFM CUBIC FEET PER MINUTE
STATIC PRESSURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
INCHES OF WATER | 0.05 | 0.1 | .125 | 0.15 | 0.2 | 0.25 | 0.3 | 0.35 | 0.4 | 0.45 | 0.5 | 0.60 | 0.70 | 1.10 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CFM | 80 | 77 | 76 | 75 | 72 | 68 | 64 | 62 | 57 | 52 | 48 | 42 | 32 | 0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The air delivery of a ventilating system may be determined by:
1.Determine the equivalent duct length for each 90 degree elbow by adding one foot of duct length for each inch of duct diameter, i.e., a 4 inch diameter duct elbow equals 4 feet equivalent duct length and an 8 inch diameter duct elbow equals 8 feet equivalent duct length.
2.Add the total straight length of duct and the equivalent length for each elbow to obtain the total equivalent duct length.
3.Locate the intersection of the fan performance curve and the total equivalent duct length curves and draw a vertical line down to the CFM scale and read the system air performance.
(NOTE: 31⁄4" x 10" duct equals 6 inch diameter duct.)
Product specifications subject to change without notice.