CDLY

0,0s...9,9s

Time setting to delete the maximum value memory after

 

 

switching point SP1 is reached (manual deletion is still possible)

 

 

 

MIN

-1 ... xxxx

Display of peak value Min

 

 

 

CLRL

-----

Delete the minimum value memory

 

 

-----

no deletion

 

 

clr

delete value

 

 

 

OFFS

-9,9 ...+xx

Measured value offset in bar

 

 

 

CUT

0,0 ... +xx

Cut-off. e.g. signal suppression at measuring range start in bar

 

 

 

DLDS

0,0 ... 9,9s

Time delay for currently displayed value in seconds

 

 

 

ERRC

-----

Error messages:

 

 

0:

-ok-

no error

 

 

1:

max

exceeding pos. measuring range

 

 

2:

min

exceeding neg. measuring range

 

 

3:

dig1

switching output 1 error

 

 

4:

dig2

switching output 2 error

 

 

5:

anao

analog output error

 

 

6:

sens

sensor error

 

 

7:

data

data error (EEProm)

 

 

8:

prog

program error

 

 

9:

cal

calibration error

 

 

 

V7.X

Lev0...Lev2

Programming lock:

 

 

Version display with actual input level:

 

 

0 :

only display of operating parameters, no changes possible

 

 

1 :

only switching points can be set (maxand min

 

 

 

memories)

 

 

2 :

release user level (all operating parameters for customer)

 

 

 

LITH

20 ... 100

Change display brightness 20...100%

 

 

(only for units with Dot-Matrix display)

 

 

 

AOZS

0 ... 9999

Scale the analog output - start value (e. g. 0 bar = 4 mA)

(only V7.X)

 

 

 

 

 

 

 

AOFS

0 ... 9999

Scale the analog output - end value (e. g. 400 bar = 20 mA)

 

 

(output signal start value always corresponds to the display ini-

 

 

tial value, e. g. 0 bar = 4mA)

 

 

Maximum turn-down 4 : 1, i.e. at values below 25 % of the mea-

 

 

suring range the analog output is switched off

 

 

 

STNO

-----

Enter the station number at Profibus DP

RECL

-----

SHRT

short profile 8 byte

 

 

LONG long profile 32 byte

 

 

 

 

selection of the Profibus-protocol

CODE

000...999

Enter the code level: Changes:

 

 

Lev1:

471

(up + down five seconds) Lev1-Lev0

 

 

Lev2:

740

(up + down + M five seconds) Lev2-Lev0

 

 

Lev0:

999

 

 

 

 

OPT

-----

Display of the unit options

(onlyV7.X)

 

 

 

 

 

 

 

 

 

5