PSW2000.qxp 6/12/2008 10:37 AM Page cov-5

1. Product Description

Dimensions (in mm)

PSW3000

Intended Applications

-The dual pressure switch monitors system pressures and has up to two switching outputs and one analog output.

-According to DESINA￿ standard

-The instruments must only be installed in systems where the maximum pressure Pmax is not exceeded (according to the values on the type label).

-Attention: This device is not designed to be used as the only safety relevant element in pressurized systems according PED 97/23/RC

2. Starting operations

Only install or uninstall the device when depressurized!

-Mount the pressure switch from bottom to the fitting with a wrench hex 36 (1/4 ) resp. 19 with 45 Nm torque.

-Electrical connection depends on the type of pressure switch (see type label) according to the chart below.

Electrical connections

Plug

Model with 1

Model with 2

Model with 1 switching

M 12 x 1,

switching output

switching outputs

output and 1 analog output

4-pin

 

(DESINA￿)

 

 

 

 

 

Pin 1

(15...32 V DC)

(15...32 V DC)

(15...32 V DC)

Pin 2

-

SP2 (0,5 A max.)

analog

Pin 3

0 V

0 V

0 V

Pin 4

SP1 (0,5 A max.)

SP1 (0,5 A max.)

SP1 (0,5 A max.)

3

Page 3
Image 3
Omega Engineering PSW2000 manual Product Description, Starting operations