Omega Engineering RHCN-7000 specifications Parameters

Models: RHCN-7000

1 2
Download 2 pages 30.38 Kb
Page 2
Image 2

PARAMETERS

 

 

PARAMETER PROGRAMMING

 

Description

Units

Range

Set Point (SP) is the only parameter the user can access with-

SP

Set Point

%

r1 to r2

out code protection.

r0

Differential or Hysteresis

%

1 to 99

Press SET. SP text will appear on the display.

r1

Low Value Set Point

%

0 to r2

• Press SET again. The real value is shown on the display.

r2

Higher Value Set Point

%

r1 to 100

• The value can be modified with the UP and DOWN arrows.

d0

Heating or Cooling Control

Option

Hu/dH

• Press SET to enter any new values.

c0

Min. stop time for Load

Minutes

0 to 59 min.

• Press SET and DOWN at the same time to quit programming

c1

Continuous Cycle Time

Hours

0 to 24 hrs

or wait one minute and the display with automatically exit

Lc

HR Value for 4 mA Input

%

0 to 100

programming mode.

Hc

HR Value for 20 mA Input

%

50 to 100

* The keyboard code can be reset to ZERO by turning off the con-

P1

Probe Adjustment (shifting)

%

0 to 10

P5

Probe Type

Range

0-1 V, 0-3 V, 4-20 mA

troller and turning it on again while keeping the SET key depressed.

H5

Parameter Access code

Numeric

0 to 99

 

(SET AT 0 FROM FACTORY)

PARAMETERS DESCRIPTION

SP = Set Point - Desired Regulation Temperature r0 = Differential or Hysteresis

r1 = Lower Set Point Limit

r2 = Higher Set Point Limit

d0 = Humidifying / Dehumidifying Control -

Humidifying: To choose Humidifying Control: Set d0 = Hu. The output is activated when the relative humidity is less than the Set Point (SP) - r0 and disconnected if the relative humidity is > = SP.

Dehumidifying: To choose Dehumidifying Control: Set

d0 = dH. The output is activated when the relative humidity is > SP + r0 and disconnected when the relative humidity is < = SP.

c0 = Minimum Times Between Start and Stop.

c1 = Continuous Cycle Time. The time the load is connected when a continuous cycle is activated. To view the programmed cycle time for display, press the down arrow button for 8 seconds. The display with blink as indicated. The output will be connected during the number of hours indicated by the

c)parameter. To cancel the Continuous cycle, press and hold the down arrow button again for 8 seconds.

Lc

= RH value for 4 mA input. Parameters for use with 4 to 20 mA

 

output probe.

Hc = RH value for 20 mA input. Parameters for use with 4 to 20

 

mA output probe.

P1

= Probe Adjustment. Offset degrees to adjust probe. If the probe

 

is not placed in the exact point that is to be measured, use a

 

standard hygrometer and adjust the difference with this

 

parameter.

P5

= Probe Type. (Set from the factory.) DO NOT ADJUST.

H5 = Access to Probe Parameters. (The code is set to 0 from the factory.)

Access to all code protected parameters.

Press SET for 8 seconds. The access code value 00 is shown on the display. (Unit comes with code set at 00 from factory).

With the UP and DOWN arrows, code can be set to user needs.

Press SET to enter the code. If code is correct, the first parameter label is shown on the display (SP).

Move to the desired parameter with the UP and DOWN keys.

Press SET to view the value on the display.

The value can be modified with the UP and DOWN arrows.

Press SET to enter the value and exit to text parameter.

Repeat until all necessary parameters are modified.

Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.

LED INDICATIONS

OUT This indicates the load is connected. The system waits for the programmed minimum stop time of the load.

DISPLAY MESSAGES

In normal operation, the humidity will be shown on the display. In case of alarm or error, the following messages will be shown:

ER = Memory Error

--= Short-Circuit Probe Error oo = Open Probe Error

In the event an error occurs, the unit follows a fixed working cycle which connects the load for 5 minutes and then disconnects the load for 5 minutes alternately.

MAINTENANCE / REPAIR

Upon final installation of the Series RHCN-7000 Digital Humidity Switch, no routine maintenance is required. A periodic check of system calibration is recommended. The devices are not field repairable and should be returned to the factory if recalibration or other services is required. After fir obtaining a Returned Goods Authorization (RGA) number, end the material, freight prepaid, to the following address. Please include a clear description of the problem plus any application information available.

Omega Engineering

Attn: Repair Department

One Omega Drive

Stamford, CT 06907

Copyright 2008 Omega Engineering, Inc.

M - 4644 / 0408

FR# R7-443649-00