Omega Speaker Systems HX93DA manual RH Measured Vs Output Reading, Temperature Output Calculations

Models: HX93DA HX93A

1 20
Download 20 pages 53.02 Kb
Page 10
Image 10

9

HX93A, HX93DA SERIES

RH/Temperature Transmitter

 

 

9. RH Measured Vs Output Reading

% Relative

Output

Humidity

Current (mA)

Voltage (Vdc)

5 4

0.8

.05

10

5.6

.10

15

6.4

.15

20

7.2

.20

25

8.0

.25

30

8.8

.30

35

9.6

.35

40

10.4

.40

45

11.2

.45

50

12.0

.50

55

12.8

.55

60

13.6

.60

65

14.4

.65

70

15.2

.70

75

16.0

.75

80

16.8

.80

85

17.6

.85

90

18.4

.90

95

19.2

.95

10. Temperature Output Calculations

To calculate Temperature by measuring the current or voltage output use the following formulas.

For Current output in ºC (-20 to 75ºC)

ºC = (Output measured in miliamps – 4) ÷ .1684 - 20 = ºC

EXAMPLE:(12.0 mA – 4) ÷ .1684 - 20 = 27.5ºC

For Current output ºF (-4 to 167ºF)

ºF = (Output measured in miliamps – 4) ÷ .0935 - 4 = ºF

EXAMPLE:(12.0 mA – 4) ÷ .0935 - 4 = 81.6ºF

For Voltage output in ºC (-20 to 75ºC)

ºC = (Output measured in volts ÷ .010526) - 20 = ºC

EXAMPLE:(0.50 Vdc ÷ .010526) - 20 = 27.5ºC

For Voltage output ºF (-4 to 167ºF)

ºF = (Output measured in volts ÷ .005848) - 4 = ºF

EXAMPLE:

(0.50 Vdc ÷ .005848) - 4 = 81.5ºF

6

Page 10
Image 10
Omega Speaker Systems HX93DA RH Measured Vs Output Reading, Temperature Output Calculations, Vdc ÷ .005848 4 = 81.5ºF