Omega Speaker Systems HX93A, HX93DA Maintenance, Specifications, Relative Humidity, Temperature

Models: HX93DA HX93A

1 20
Download 20 pages 53.02 Kb
Page 17
Image 17

HX93A, HX93DA SERIES

16

RH/Temperature Transmitter

16. Maintenance

If your Humidity transmitter will be used in a dusty environment, the protective sensor filter, if clogged, may be removed for cleaning. Unscrew the protective cover and gently blow compressed air through the filter screen. A soft brush may also be used to remove dirt particles from the screen.

If the sensor is subjected to 100% condensation, it must be dried to obtain correct readings. There will be no permanent damage or calibration shift to the unit.

Units should not be exposed to high concentrations of ammonia or alcohol vapors.

17.Specifications

Relative Humidity

Measuring Range: Accuracy:

Repeatability:

Operating Temperature Range:

Output:

Model: HX93AC

Model : HX93AV Power:

Max Loop Resistance:

RH Time Constant (90% response at 25ºC, in moving air at 1m/s):

3 - 95% (non-condensing)

±2.5% @ 72ºF with an added temperature coefficient error of -.06% RH/ºF (both increasing and decreasing in temperature).

± 1 % RH

-20 to 75ºC (-4 to 167ºF)

4 to 20 mA (Scaled for 0 to 100% RH) 0 to 1 Vdc (Scaled for 0 to 100% RH)

6 –30 Vdc @ 20mA

Ohms = (V supply – 6 V)/.02 A

>10 seconds, 10 to 90% RH >15 seconds, 90 to 10% RH

Sensor Type:

Thin Film Polymer Capacitor

 

Temperature

 

 

Measuring Range:

-20 to 75ºC (-4 to 167ºF)

 

Accuracy:

± 0.6ºC (1ºF)

 

Repeatability:

± 0.3ºC (0.5ºF)

 

Output:

4 to 20 mA (Scaled for 0 to 100% RH)

 

Model: HX93AC

 

Model : HX93AV

0 to 1 Vdc (Scaled for 0 to 100% RH)

 

Power:

6 -30 Vdc @ 20mA

 

No Displays

13

With Displays

12 - 30 Vdc @ 30mA

Page 17