CURRENT SOURCING SENSOR

Enabling the Front Panel Reset Key

The fourth screen in the program mode allows you to enable or disable the front panel reset key.

Press the m key to choose the option you want.

Note: The reset terminal on the rear panel is still active when the front reset button is disabled.

Note: To exit the program mode, disconnect the jumper between terminals 1 and 5.

WIRING RECOMMENDATIONS

Following these suggestions will increase noise immunity and lengthen unit life.

Cable: Make the connection between the count source and the totalizer with a two-conductor shielded cable. Connect the shield to earth ground at one end only.

Relay Coil Suppression: If a relay contact is used as a count source, suppress the relay coil. This can be accom- plished with an RC network for AC coils or a diode for DC coils.

Mounting: Do not mount the totalizer near a solenoid or other inductive devices. Supply enough ventilation to keep the totalizer operating within the temperature specifications. Do not mount this unit in a heavy vibration area.

WIRING DIAGRAMS

SOLID STATE ADD/SUBTRACT INPUT (DPClO-CS)

CURRENT SOURCING SENSOR

SOLID STATE ADD/SUBTRACT INPUT (DPClO-CS)

CURRENT SINKING SENSOR

+6 to +28 VDC

,

Sensor

CONTACT CLOSURE COUNT INPUT (DPClO-CC)

PROGRAM MODE ENABLE (All Models)

REMOTE RESET (All Models)

[_Zk

BATTERYSAFETY

The lithium battery that powers your device contains inflam- mable materials such as lithium organic solvent, and other chemical ingredients. Explosion or fire may result if the battery is not handled correctly. To avoid an accident follow these guidelines:

??Do not heat batteries above 95°C

??Do not recharge lithium batteries

??Do not dispose of batteries in fire

??Insert battery with correct polarity

Terminal Function

1Ground

2Input B Count input

3Input A Count Input

4Reset

5Program Enable

Operation

Current Source Input (DPClO-CS) Current Sink Input (DPClO-CC)

Current Source Input (DPCIO-CS) Current Sink Input (DPCIO-CC)

Connect through Contact

Closure to Ground

Connect to Ground to Enter Program Mode

Page 4