OPERATION
Step 1. Apply Power to the Instrument
When your device is first powered up it will display the ambient temperature (assume 75°F).
Step 2. Enter Setpoint 1 Menu
Press a one time from run mode to get to SP1 Setpoint 1.
Step 3. Enter the Setpoint 1 Value Submenu
Press d. Display shows the previous selection of Setpoint 1.
Step 4. Change the Setpoint 1 Value
Press b or c until desired value is displayed.
Step 5. Store the Setpoint 1 Value
Set the Setpoint 1 to 10 degree higher than Process value (SP1 = 85) and press d to store, display flashes STRD message and advances to SP2 Setpoint 2 Menu.
Step 6. Store the Setpoint 2 Value
Repeat steps 3 and 4. Set the Setpoint 2 to 5 degree higher than Process value (SP2 = 80) and press d to store, display flashes STRD message and advances to CNFG Configuration Menu.
Step 7. Enter the Reading Config Menu
Step 17. Enter Alarm 1 Enable/Disable Submenu
Press d to display flashing DSBL/ ENBL.
Step 18. Enable Alarm 1 Submenu
If flashing ENBL is displayed, press a, if DSBL is displayed, press b until ENBL is displayed, then press d to store and go to the next menu item.
Step 19. Select the Deviation Control Type Submenu
Press d. If flashing _DEV Deviation is displayed press a, otherwise press b until flashing _DEV is shown. Now press d to store and go to next menu item.
Step 20. Select the Latched Type Submenu
Press d. If flashing UNLT Unlatched is displayed press a, otherwise press b until UNLT is displayed.
Press d to store and advance to next menu item.
Step 21. Select the Normally Open Type of Contact Closure Submenu
Press d. If flashing N.o. Normally Open is displayed, press a, otherwise press b until N.o. is displayed. Press d to store and advance to next menu item.
Step 22. Select the Above Type of Active Submenu Press d. If flashing ABoV Above is displayed, press a, otherwise press b until ABoV is displayed. Press d to store
SPECIFICATION
SENSOR SPECIFICATIONS Relative Humidity Accuracy/Range:
±2% for 10 to 90% RH
±3% for 0 to 10%RH and 90 to 100%RH
Hysteresis: ±1% RH
Response Time:
4 sec (63% slowly moving air)
Repeatability: ±0.1%
Resolution: 0.03%, 12bit
Temperature Accuracy/Range*: ±1°C (±2°F) for
±0.5°C (±1°F) for 0 to 80°C (32 to 176°F)
*NOTE: extended temp range is for Probe only, the Controller’s operating temp is
Repeatability: ±0.1°C
Resolution: 0.01°C, 14 bit
METER SPECIFICATIONS
Display:
•10.2 mm (0.40"):
•10.2 mm (0.40") and 21 mm (0.83"):
Red, green, and amber programmable colors for setpoint and temperature units.
Output 1†:
Relay 250 Vac @ 3 A Resistive Load, SSR, Pulse
Output 2†:
Relay 250 Vac @ 3 A Resistive Load, SSR, Pulse
†Only with
Options: Communication
Exc. not available for Low Power Option
Line Voltage/Power:
90 - 240 Vac ±10%, 50 - 400 Hz*, or 110 - 375 Vdc, 5 W
* No CE compliance above 60 Hz
Low Voltage Power Option:
12 - 36 Vdc, 3 W**
**Units can be powered safely with 24 Vac but No Certification for CE/UL are claimed.
Dimensions:
Dual Horizontal: 48H x 96W x 127D mm (1.89 x 3.78 x 5")
Dual Vertical: 48W x 96H x 127D mm (1.89 x 3.78 x 5")
Weight:
295 g (0.65 lb)
Approvals:
CE per
MADE IN
USA
DPiTH-i8DH, DPiTH-i8DV
Press d to enter RDG Reading Config Menu.
Step 8. Enter the submenu items of Rdg Config Menu
Press d to display SNSR Sensor submenu: Sensor selection for Autotune, Loop, or Ramp and Soak °F.°C is for
temperature and DRRh is for Humidity
Step 9. Enter the submenu items of Rdg Config Menu
Press d to display Temp Unit submenu:
Step 10 Scroll thru selection for Temp Unit submenu
Press b to Scroll though the available selections of the Temperature Unit of your choice: °F or °C.
Step 11. Store the Temperature Unit
Press d, display momentarily shows STRD the Unit has been stored and the instrument will go automatically to the next menu item.
Step 12. Enter the Filter Constant Submenu
Display shows FLTR Filter Constant Submenu.
Step 13. Display the Filter Constant Value Submenu
Press d to display the flashing, previously selected Filter Constant.
Step 14. Scroll through available Filter Constants
Press b to sequence thru Filter Constants 0001, 0002, 0004, 0008, 0016, 0032, 0064 and 0128.
Step 15. Store the Filter Constant
Press d momentarily to store 0004 Filter Constant and the instrument will automatically go to the next menu item.
Step 16. Enter Alarm 1 Menu
The display will show ALR1 the top menu for Alarm 1. In the following steps we are going to enable Alarm 1, Deviation, Unlatch, Normally Open, Active Above, Enable at
•If Analog Output Option is installed and enabled, the controller will skip Alarm 1 Menu item to Analog Output.
•Alarm must be DISABLED if Ramp is ENABLED.
•Alarm1 will only work for Humidity, not Temperature.
Alarm 1 is designed to monitor the humidity value around Setpoint 1 and Alarm 2 is designed to monitor the temperature value around Setpoint 2.
and advance to next menu item.
Step 23. Enable Alarm 1 at Power On (A.P.oN)
Press d. If flashing ENBL is displayed, press a, otherwise press b until ENBL is displayed. Press d to store and advance to next menu item.
Step 24. Enter Alarm 1 High Submenu
Press a twice to skip ALR.L Alarm 1 Low value. ALR.L is for below & ALR.H for above.
Step 25. Set the Alarm 1 High value (ALR.H)
Press d. Press b or c until value to set the display to
002.0. Press d to save.
Step 26. Enter the Alarm 2 Menu
The display will show ALR2 the top menu for Alarm 2. Repeat steps from 17 to 25 to set for Alarm 2 the same conditions as for Alarm 1.
Step 29. Configuration of Display Color Selection
Press a until the COLR Display Color Selection Menu appears on the Display. Configure COLR as N.CLR / GRN (green), 1.CLR / RED (red), 2.CLR / AMBR (amber). Please
refer to the operator’s manual if needed.
For color change on Setpoints refer to Owners Manual Section 2.
WARNING: These products are not designed for use in, and should not be used for, patient- connected applications.
This device is marked with the international caution symbol. It is important to read the Setup Guide before installing or commissioning this device, as the guide contains important information relating to safety and EMC.
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OEMGA is constantly pursuing certification of its products to the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
TRADEMARK NOTICE:
® , omega.com® , ® , and ® are Trademarks of
OMEGA ENGINEERING, INC.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of one (1) year from the date of purchase. In addition to OMEGA’s standard warranty period, OMEGA Engineering will extend the warranty period for four (4) additional years if the warranty card enclosed with each instrument is returned to OMEGA.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the | FOR | ||
following information available BEFORE | current repair charges. Have the following information | ||
contacting OMEGA: | available BEFORE contacting OMEGA: | ||
1. | Purchase Order number under which the product | 1. | Purchase Order number to cover the COST of the |
| was PURCHASED, |
| repair, |
2. | Model and serial number of the product under | 2. | Model and serial number of product, and |
| warranty, and | 3. | Repair instructions and/or specific problems |
3. | Repair instructions and/or specific problems |
| relative to the product. |
| relative to the product. |
|
|
|
|
|
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
©Copyright 2005 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or
PATENT AND TRADEMARK NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No. Des. 336,895; 5,274,577; 6,243,021 / CANADA 2052599; 2052600 / ITALY 1249456; 1250938 / GERMANY DE 41 34398 C2 / SPAIN 2039150; 2048066 / UK Patent No. GB2 249 837; GB2 248 954 / FRANCE BREVET NO. 91 12756. The “Meter Bezel Design” is a trademark of Newport Electronics, Inc. USED UNDER LICENSE. Other U.S. and International Patents pending or applied for.
MQS4003/1105
Humidity + Temperature Monitor
CNiTH-i8DH-AL, CNiTH-i8DV-AL
Humidity + Temperature Limit Alarm
|
|
| ® |
|
|
| ® |
|
|
| |
OMEGAnet® |
| Internet | |
www.omega.com |
| info@omega.com | |
|
|
| |
| Servicing North America: | ||
USA: | One Omega Drive, P.O. Box 4047 | ||
ISO 9001 Certified | Stamford CT |
| |
| TEL: (203) | FAX: (203) | |
|
| ||
Canada: | 976 Bergar |
| |
| Laval (Quebec) H7L 5A1 |
| |
| TEL: (514) | FAX: (514) | |
|
|
For immediate technical or application assistance:
USA and Canada: | Sales Service: | |
| Customer Service: | |
| Engineering Service: | |
Mexico and | TEL: | FAX: (001) |
Latin American: | En Español: (001) |
|
|
| |
| Servicing Europe: |
|
Benelux: | Postbus 8034, 1180 LA Amstelveen, The Netherlands | |
| TEL: +31 20 3472121 | FAX: +31 20 6434643 |
| Toll Free in Benelux: 0800 0993344 | |
|
| |
Czech Republic: | Frystatska 184, 733 01 Karviná |
|
| TEL: +420 59 6311899 | FAX: +420 59 6311114 |
|
| |
France: | 11, rue Jacques Cartier, 78280 Guyancourt | |
| TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27 | |
| Toll Free in France: 0800 466 342 |
|
|
| |
Germany/Austria: | Daimlerstrasse 26, | |
| TEL: +49 7056 | FAX: +49 7056 |
| Toll Free in Germany: 0800 639 7678 | |
|
| |
United Kingdom: | One Omega Drive |
|
ISO 9002 Certified | River Bend Technology Centre |
|
| Northbank, Irlam Manchester M44 5BD United Kingdom | |
| TEL: +44 161 777 6611 FAX: +44 161 777 6622 | |
| Toll Free in England: 0800 488 488 |
|
|
|