FSW-410 Series
Thermal Flow Switches
TECHNICAL INFORMATION
FSW-410 SERIES
The safe sensing solution for industrial cooling systems.
The
The
Compact electronic unit with no moving parts
No adjustment or calibration needed
Maintenance free
Fail safe normally open switch
Easy to Install
Technical Data
Type
Medium
Sensor Data
Low Flow Set Point Hi Temp Set Point Medium temperature Response time Repeatability Hysteresis Pressure
Mechanical Data
Protection class Housing Material Thread Connection
Electrical Data
Operating voltage Switching current Power Consumption Initial Operation Electrical Output
Water based liquid
0.3 m/s (.9 fps) (water related)
50°C (122°F) or 70°C (158°F), other settings possible on OEM
5 – 10 seconds
< 0.5 %
approx. 20% of setpoint value
10 bar (150 PSI)
IP 67 (NEMA6)
Stainless Steel 1.4301 (303)
½ “
M12 male socket, 4 pin + 2m connection cable with M12 connector
18 to 30 V DC, incl. residual ripple
200mA 4 W max.
after 15 seconds
PNP n.o. (switch closed with flow)
Part Number Key: | Example: |
|
|
| Connection diagram | ||
Temp Setpoint (°C), | code: | 50nc |
|
|
|
| 1 - brown |
Flow Set Point (m/s), | code: | .3no |
|
|
|
| 4 - black |
Sensor Head Length, | code: | 50.5mm |
|
|
|
| |
|
|
|
| 3 - blue | |||
Thread | code: | 1/2” NPT |
|
|
| ||
|
|
| 2 | ||||
|
|
|
|
|
|
| |
| 27 Sechsk./Hex | Connector12M Stecker12M | G1/2 A | 27 Sechsk./Hex | Connector12M 12MStecker | ||
|
|
|
|
|
|
| |
|
|
| 413,415 |
|
|
| |
D 17 |
|
|
| D 17 |
|
|
|
50.5 | 12 | 12.5 | 12 |
|
|
| |
73 |
|
| 35 |
93 |
|
| 55 |
V DC
Load