Omron E5ZN-DRT Connections, Characteristics, Communications for Temperature Controller Expansion

Models: E5ZN-DRT

1 9
Download 9 pages 2.66 Kb
Page 4
Image 4
■Characteristics

E5ZN-DRT

Characteristics

Insulation resistance

20 MΩ min. (at 100 VDC)

 

 

 

 

Dielectric strength

500 VAC, 50/60 Hz for 1 min between the DIN track and all DeviceNet connector terminals and between the DIN track

 

and all terminal socket terminals

 

 

 

 

 

Vibration resistance

10 to 55 Hz, 10 m/s2 for 2 hrs each in ±X, ±Y, and ±Z directions

 

Shock resistance

150 m/s2, 3 times each in ±X, ±Y, and ±Z directions

 

Weight

100 g max.

 

 

 

 

 

 

 

 

Safety standards

cULus508

 

 

 

 

EMS:

Electrostatic Discharge (ESD)

EN61006-2, EN61000-4-2 (4 kV/contact, 8 kV/air)

 

 

Radiated Electromagnetic Fields

EN61006-2, EN61000-4-3 (10 V/m)

 

 

 

Electrical Fast transients/BURST

EN61006-2, EN61000-4-4 (2 kV/DC power-line, 1 kV/Signal-line)

 

 

Surge Transients

EN61006-2, EN61000-4-5 (line to ground

: 1 kV/DC power-line)

 

 

 

 

: 2 kV/Signal-line

 

 

 

line to line

: 0.5 kV/DC power-line)

 

 

Conducted Disturbances

EN61006-2, EN61000-4-6 (10 V)

 

 

EMI:

Radiated Emissions (electric field)

EN50081-2 Class A

 

 

 

 

 

 

Communications (for Temperature Controller Expansion)

Transmission line

RS-485 multipoint

connection method

 

 

 

Communications method

RS-485 (2-wire, half-duplex)

 

 

Synchronization

Start-stop synchronization

method

 

 

 

Baud rate

38,400 bps

 

 

Transmission code

ASCII

 

 

Data bit length

7 bits

 

 

Stop bit length

2 bits

 

 

Error detection

Vertical parity (even)

 

 

 

BCC (block check character)

 

 

Flow control

None

 

 

Number of Units that can

16 Units max. (32 channels)

be connected in parallel

 

Connections

Terminal Arrangement

E5ZN-DRT

Color

Signal

Red

Communications power, positive (+V)

White

Communications signal, high (CAN H)

---Shield

Blue

Communications signal, low (CAN L)

Black

Communications power, negative (–V)

10

MS

NODE

 

ADR

NS

1

 

ON

 

UP/DN

TS

COPY

 

E5ZN-SCT24S

+

External input power

 

supply (24VDC)

 

Setting Display Unit

communications

 

Communications for

Temperature

Controller expansion

(TOP VIEW)

19

13

7

1

20

14

8

2

B (+)

15

9

3

21

A ()

16

10

4

22

B (+)

17

11

5

23

A ()

18

12

6

24

Not used with the DeviceNet Communications Unit

http://www.ia.omron.com/

(c)Copyright OMRON Corporation 2007 All Rights Reserved.

4

 

 

 

 