TWO WIRE START GENERATOR HOOK UP
GENERATOR
12V RELAY
NO |
| COIL | |
NC | COM | ||
| |||
|
|
FX INVERTER/CHARGER
INVERTER
ON/OFF
AUX +
AUX -
XCT -
XCT +
There are two screw terminals for each relay contact. Each can handle up to 8 amps. They are tied together internally.
COM 11 and COM 21 are the common relay connections. Either can be used for loads under 8 amps. If the load exceeds 8 amps, use both COM 11 and COM 21.
r NO 14 and NO 24 are normally open relay connections. Use both 14 and 24 terminals for loads exceeding 8 amps.
r NC 12 and NC 22 are normally closed relay connections.
Use both 12 and 22 terminals for more than 8 amps.
NOTE: If a load exceeds 8 amps, use both screw terminals for any given relay contact to distribute the current and avoid overloading the screw terminal.
Terminal screw torque – 0.5 Nm (4.4 inch lbs)