•DC Genset. Normally, the FX inverter requires AC input to make certain the generator started. If you need to use a DC generator instead, you can tell the AGS not to look for AC input. AGS stops the generator when the DC voltage rises to a certain value. (This does not guarantee good battery charging. Also, the AGS has to take it on faith that the generator has even started.)
You do not have to select one function over another — the AGS can start the generator for any reason. If you don’t know why the generator started, a MATE menu can tell you.
Starting Functions: Battery SOC
The OutBack FlexNet DC sends battery
Without the MATE
The AGS functions, including SOC, are based in the MATE itself and are programmed in the MATE’s own menu area. If the MATE cannot be installed or must be removed for some reason, AGS cannot be used.
The OutBack FX inverter has a function of its own called GenAlert. GenAlert will energize the AUX output upon reaching low battery voltage for a certain amount of time, and will turn off the output after reaching a high voltage for a certain time (all settable). This can allow the inverter to automatically start the generator, even if there is no MATE. (However, this may not allow the full charge cycle.) The MATE must still be used for the initial setup, in the FX section of the menus.
The OutBack FlexNet DC has an AUX switch of its own. This is a set of dry contacts, instead of a
AGS and AUX Selection
AGS can only send commands to one AUX at a time. You can connect the
Stopping
The AUX removes its output to stop the generator, whether operating by AGS, GenAlert, FlexNet DC. A
AGS can perform generator cooldown. It will disengage the inverter from the generator for a selectable time before sending the stop command, to keep the generator from stopping while under load. Similarly, AGS can also perform generator warmup, while starting. These functions are only present for AGS.