Planning
900-0113-01-00 Rev A 13
Generator Sizing

A generator should be sized to provide enough power for all the loads and the battery charger.

Available generator power may be limited by ratings for circuit breakers and/or generator connectors.
The generator must be able to provide current to all inverters on a given phase or leg. Minimum generator
wattage* is usually recommended to be twice the wattage of the inverter system. Many portable generators
may not be able to maintain AC voltage or frequency for long periods of time if they are loaded more than
80% of rated capacity.
(*after de-ratings for peak versus continuous power, for load power factor considerations, for altitude, and
for ambient temperature.)
A generator that is to be installed in a building should not have a bond between the neutral and ground
connections.
In addition, if a split-phase 120/240 Vac generator is powering a single-phase 120 Vac inverter system with
no other compensation, it is required to be at least twice the wattage of the inverters. (A split-phase
generator that is heavily loaded on one output leg may suffer severely from balancing issues.) The OutBack
FW-X240 or PSX-240 balancing transformers may compensate for this condition.