Panasonic 3309 manual

Models: 3309

1 2
Download 2 pages 47.45 Kb
Page 2
Image 2
3309

 

 

 

Type numbers

 

 

3309

Enclosed analog heat detector (incl. conn. box, 3 compr. glands and gasket)

 

 

3390

Label holder (100 holders per packet, excl. labels)

 

 

 

 

 

 

 

 

 

 

 

 

 

3391

Labels for 3390 (10 sheets à 132 labels)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection box mounting holes (2 x 5 mm) c/c = 108 mm. The connection box is prepared for required number of

compression glands, two (in / out) or three (in / out / ext.

LED). A gland is approx. 30 mm high.

Detector mounting holes, (2 x 4 x 7 mm) c/c = 70 mm. SA / SB (Red/White) = COM loop in and out respectively. One SA and one SB connector is provided with a short "wire" to be used to connect the Address setting tool 3314 during mode and address setting. The "wires" are to be pulled out before the COM loop wires are connected. E+ / E- = Ext. LED (cable length max. 30 m). Connectors for wire diameter 0.6 – 1.2 mm (0.3 – 1.13 mm2 approx.).

 

 

 

 

 

 

Technical data

 

 

 

 

 

 

 

 

 

 

 

Voltage (V DC)

 

 

 

 

 

 

 

 

 

rated

28

 

 

 

 

 

allowed

12-30

 

 

 

normal (on the COM loop)

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current consumption at norm. volt.

 

 

 

 

 

 

 

 

 

(mA)

 

 

 

 

 

 

 

 

 

quiescent

0.185

 

 

 

active (incl. internal LED)

1.650

 

 

 

ext. LED

< 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal capacitance (nF)

0

 

 

 

 

 

 

 

Internal inductance

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient temperature (°C)

Depending on the mode.

 

 

operating

NORMAL mode (Class is depending on the algorithm)

(Min. / Typical / Max.)

Class A1: -20 /+25 /+50, A2 S: -20 /+25 /+50 or B S: -20 /+40 /+65

(Min. / Typical / Max.)

2330 mode: -20 /+25 /+50

storage

-45 to +70

 

 

 

 

 

 

 

 

 

 

 

Ingress Protection rating

 

IP67 (attached connection box, silicon gasket and compression glands

 

are required)

 

 

 

 

 

 

 

 

 

 

Sensitivity (°C)

NORMAL mode: Depending on the algorithm.

 

Static response temperature (range)

Class A1: 54-65, A2 S:

54-70 & B S: 69-85

 

2330 mode: Class A2 S:

57

 

 

 

 

 

 

 

 

 

 

 

Size ∅ x H (mm)

100 x 78

 

 

 

 

 

 

 

 

 

 

 

 

Weight (g)

Detector: 112

Connection box (incl. 3 glands): 134

 

 

 

 

 

 

 

 

Construction / Colour

Modified Polycarbonate / Grey (N8, Munsell colour code)

 

 

 

 

 

 

 

Approvals

 

 

 

 

 

05 EC Certificate no. 0845-CPD-232.1190

 

 

 

 

 

 

 

 

 

NORMAL mode: EN54-5:2000: Class P (depending on algorithm).

 

2330 mode: EN54-5:2000: Class A2 S.

 

 

 

 

 

 

 

 

 

 

ATEX classification

 

 

 

 

II 3GD EEx nA II T5 (T70°C), -20°C Ta 65°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00133

2001-10-19

8 / 2008-10-10

 

 

 

Page 2
Image 2
Panasonic 3309 manual