Panasonic 4300 manual

Models: 4300

1 2
Download 2 pages 22.73 Kb
Page 2
Image 2
Manual background

Type number

4300

Analog multi detector

Lsh

Tl

 

E-

 

Ls

SB

E+

Al

 

SA

 

The detector is plugged in the analog base 3312x / 4313. The COM loop / Ext. LED are connected to the analog base.

SA (L) 3312

4313

3312FL/F

 

 

SB (C)

 

 

 

 

COM loop

 

EBL128/ input

 

 

 

 

 

 

 

 

Mark

 

 

Mark

Mark

 

 

 

 

 

 

 

 

SB

SA

Ext. LED

SAi SB SAo

SB

SA

EBL512C.i.e.

COMloop

 

 

 

 

 

E-

E+

+

E-

E+

E-

E+

 

 

 

 

 

 

 

 

 

SA (L)

 

 

 

 

 

 

 

 

SB (C)

 

 

 

 

 

 

In the detector:

See also "Engineering Instructions for detectors Type 430x".

SA/SB Contact pins for COM loop / address setting tool 3314

E+/E- Contact pins for External LED

Tl

Type number label;

Detector type

Al

Address label; For the programmed COM loop address to be written.

Lsh

Locking screw hole (prepared for drilling through detector body)

Ls

Locking screw

 

Prepared for mechanical locking with analog base 3312x / 4313. One hexagon socket screw (Ls) is attached (1.5 mm Hex key to be used). The 2.5-2.7 mm hole (Lsh) has to be drilled.

 

 

 

 

 

Technical data

 

 

 

 

 

 

 

 

 

 

Voltage (V DC)

 

 

 

 

 

 

 

rated

28

 

 

 

 

allowed

12-30

 

 

normal (on COM loop)

24

 

 

 

 

 

 

 

 

 

 

 

 

Current consumption at nom. volt.

 

 

 

 

 

 

 

from COM loop (mA)

 

 

 

 

 

 

 

quiescent

0.3

 

 

 

 

active (incl. internal LED)

2.3

 

 

 

 

ext. LED (connected via base 3312)

max. 2

 

 

 

 

 

 

 

 

 

 

Ambient temperature (°C)

 

 

 

 

 

 

 

operating

-10 to +50

 

 

storage

-25 to +75

 

 

 

 

 

 

 

 

 

 

Ambient humidity (% RH)

max. 95, non condensing

 

 

 

 

 

 

 

 

 

 

Ingress Protection rating (estimated)

IP 51

 

 

 

 

 

 

 

 

 

 

Sensitivity (obscuration; %/m)

Depending on mode.

 

 

NORMAL mode

3.6 / 3.0 / 2.4 (Low / Normal / High)

 

 

2330 mode

5

 

 

 

 

 

 

 

>2.5 in combination with temp. rate-of-rise (depending on algorithm)

 

 

 

 

 

 

 

 

Sensitivity (T=°C; deltaT=°C/min.)

Depending on mode.

 

 

NORMAL mode

56 / 46 / 60 / 74 (A1; < 4 / A1; > 4 / A2 (S) / B (S))

2330 mode

57; 6.43

 

 

 

57; >1.07 in combination with smoke obscur. (depending on algorithm)

 

 

 

 

 

 

 

 

Size x h (mm)

102 x 44

 

 

 

 

 

 

 

 

 

 

Weight (g)

70

 

 

 

 

 

 

 

 

 

 

 

Construction / Colour

Modified polycarbonate / Grey (N8, Munsell colour code)

 

 

 

 

 

 

 

Approvals

 

 

 

 

05 EC Certificate no. 0786-CPD-20145;

EN54-7 (smoke)

 

 

 

 

 

 

 

 

 

05 EC Certificate no. 0786-CPD-20146;

EN54-5 Class P (heat)

 

 

 

 

 

 

 

 

 

 

 

 

 

All technical features and data are subject to changes without notice, resulting from continuous development and improvement.

Product Leaflet

Date of issue

Revision / Date of revision

MEW00307

2003-04-24

6 / 2008-09-15

 

 

 

Page 2
Image 2
Panasonic 4300 manual