•Conventional heat detector
•Fixed temperature (static) alarm level
Fixed temperature alarm level
The conventional fixed temperature (static) heat detectors will give an alarm within a static response temperature range, within a specified response time, in accordance with
The heat sensitive element is a thermistor.
The detector is plugged in a conventional detector base 2324, connected to a conventional zone line input. An LED on the base will light up when the detector goes into alarm. The base also has an output for an external LED, e.g. 2218.
4375 and 4376
The following types are available (type number, temperature and class):
4375, 60°C, class A2 S.
4376, 80°C, class B S.
Latching
The detectors are latching, i.e. they will not be automatically reset if the temperature, after the alarm, falls below the detector's static response temperature. The LED in the base and a connected external LED will be lit until the detector is reset via the c.i.e.
Fire alarm systems
Heat detectors 4375 and 4376
Environment friendly
The detectors have unleaded soldering. The latest IC technology reduces the number of semiconductors and other electronic components to a minimum. The detectors fulfils the RoHS Directive.
Product applications
The detectors can be used in the systems EBL500 / 512 / 128 / 1000 / 2000 provided with some zone line inputs for the system respectively (e.g. an 8 zones expansion board 1580 / 4580 zone line input, an addressable multi purpose I/O unit 3361 zone line input, etc.).
Heat detectors are normally used in rooms where the temperature can be expected to rise rapidly in case of a fire or places where smoke detectors can not be used.
The detectors are intended for indoor use and in dry premises premises.