Fire alarm system
EBL128
4550
•EBL128, an intelligent analog addressable fire alarm system for up to 128 addresses
•Auto generation of the Site Specific Data for easier c.i.e. programming
Analog addressable system
EBL128 is an intelligent analog addressable fire alarm system, conforming to the
Features / functions
A
An SSD Auto generation function is included in Win128. The units that are connected to EBL128 can be identified and the SSD can be auto generated with default settings and be edited before the download.
Some other features / functions:
•Compensation for contamination, i.e. analog smoke detectors have constant sensitivity in spite of any contamination. A Service signal will be given when a detector has to be replaced.
•Advanced alarm algorithms are used to filter the nuisance alarms from the real fire alarms and one algorithm is used for detection of smouldering fires.
•User related functions, e.g. Test mode, Disablements, Alert annunciation, Fire door closing, Interlocking combinations of outputs & inputs, Time channels, Co- incidence alarm, User definable text message for each alarm point, etc.
•Programmable inputs and outputs. In the c.i.e. and/or via I/O units on the COM loop. A large number of trigger conditions are available.
•Outputs for routing equipment. Fire alarm, Fault and Power supply.
•Socket for an optional RS485 transceiver component to provide an interface for up to four ext. Fire Brigade Panels, Ext. Presentation Units and/or Alert Annunciation Units.
•Interface (RS232) for a PC (Win128)
•Interface (RS232) and power supply for
Optional RS485 transceiver 4552, provides an interface for up to four display units.
Optional expansion boards 458x mounted in an exp. board holder 4551 provides 8 zone line inputs and 8 relay outputs respectively.
Up to 128 addresses
The EBL128 c.i.e. has one COM loop for connection of the loop units (address 001- 127). Each loop unit uses one address.
Some loop units that can be connected:
•Analog heat & smoke detectors
•Addressable manual call points
•Addressable short circuit isolators
•Addressable input and output units (to which e.g. conventional detectors and manual call points can be connected)
•Addressable sirens & sounder bases
•Addressable external power supply units
Miscellaneous
The cabinet has a space for two sealed
EBL128 is intended for indoor use and in dry premises.
Panasonic Electric Works Fire & Security Technology Europe AB Citadellsvägen 23,
Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99