PB Heat MI/MIH series manual Electrical, Intermittent Ignition see .3 above

Models: MI/MIH series

1 43
Download 43 pages 13.15 Kb
Page 20
Image 20
2. Intermittent Ignition (see Figure 6.3 above)

ELECTRICAL

Figure 6.3: Wiring and Connection Diagram – Intermittent Ignition

2. Intermittent Ignition (see Figure 6.3 above)

a.The vent damper is continuously powered. On a call for heat, limit relay R is energized, which energizes:

the circulator (when used) through contact R1, and

the vent damper operator through contact R2, provided that the high-limit aquastat switch is closed.

The damper operator opens the vent damper.

b.Once the damper is proven open, the ignition circuit within the gas valve energizes, provided that all of the following conditions are met:

the blocked vent switch is closed, and

the flame rollout switch is closed.

c.When the call for heat ends:

Limit relay R de-energizes, which opens contacts R1 and R2.

The circulator shuts down.

The gas valve de-energizes.

The vent damper closes.

d.If temperature exceeds limit setting, main burners shut off and circulator continues to operate.

18

Page 20
Image 20
PB Heat MI/MIH series manual Electrical, Intermittent Ignition see .3 above