5 - Electrical Installation

For safety purposes, only competent personnel should perform the electrical installation. All equipment should be installed to current Electrical Regulations and Standards.

In order to obtain the maximum light output from the searchlight, it is essential that the full operating voltage of the lamp fitted be applied to the lampholder contacts.

Method of Electrical Connection

1)Disconnect the supply before working on the electrical system;

2)The searchlight must be connected to a fused electrical supply, using suitably sized cable;

3)If the searchlight is located a considerable distance from the supply, provision must be made in the cable size in order to overcome the voltage drop.

The following table below indicates the maximum length of cable to be used for the AC supply cable, from the control panel to the searchlight:

Searchlight

120v 2Kw

230v 2Kw

240v 2Kw

115v 3Kw

230v 3Kw

Cable Size (mm²)

Distance Max

Distance Max

Distance Max

Distance Max

Distance Max

2.5

15 MTRS

55 MTRS

60 MTRS

9 MTRS

37 MTRS

4

24 MTRS

88 MTRS

96 MTRS

14 MTRS

58 MTRS

6

37 MTRS

137 MTRS

150 MTRS

22 MTRS

91 MTRS

10

62 MTRS

230 MTRS

251 MTRS

38 MTRS

153 MTRS

4)Whenever possible cable terminations should be made below deck and with approved terminal devices;

5)If a spare auxiliary fuse or circuit breaker is not available, one of the correct type and rating should be fitted and connected to a positive supply. It is advisable to locate a bus bar or main connection and avoid any direct connection to the supply:

6)For 110/220v AC products, the following colour coding system should be used for the customer supply cable:

Brown

- Live

Blue

- Negative

Green/Yellow

- Earth

Note: This equipment must be earthed.

Page 7
Image 7
Pelco L560 installation manual Method of Electrical Connection