CABLE CONNECTIONS AND REQUIREMENTS

Table A. Wiring Distances

The following are the recommended maximum distances to wire the WCS1-4 to a Spectra III or Esprit positioning system.

To determine the correct voltage tap:

1.Pick the unit type.

2.Find the wire gauge used (22 gauge is not recommended).

3.Determine which secondary output tap (A, B, or C) is appropriate for the distance between the dome or positioning system and the WCS1-4. Distance is in feet (meters).

MAXIMUM DISTANCE FROM TRANSFORMER TO LOAD

Spectra III Indoor (25 VA)

20 AWG

18 AWG

16 AWG

14 AWG

12 AWG

(0.5 mm2)

(1.0 mm2)

(1.5 mm2)

(2.5 mm2)

(4.0 mm2)

Tap A (24 VAC)

113 (34)

180 (55)

287 (87)

455 (139)

725 (221)

Tap B (26 VAC)

133 (40)

212 (64)

337 (103)

536 (163)

852 (260)

Tap C (28 VAC)

155 (47)

246 (75)

392 (119)

623 (190)

990 (302)

Environmental Spectra III and

20 AWG

18 AWG

16 AWG

14 AWG

12 AWG

Esprit with IOC & IOP (70 VA)

(0.5 mm2)

(1.0 mm2)

(1.5 mm2)

(2.5 mm2)

(4.0 mm2)

Tap A (24 VAC)

41 (12)

64 (19)

102 (31)

163 (50)

259 (79)

Tap B (26 VAC)

49 (15)

78 (24)

124 (38)

198 (60)

315 (96)

Tap C (28 VAC)

55 (17)

88 (27)

135 (41)

222 (68)

353 (107)

Esprit (50 VA)

20 AWG

18 AWG

16 AWG

14 AWG

12 AWG

(0.5 mm2)

(1.0 mm2)

(1.5 mm2)

(2.5 mm2)

(4.0 mm2)

Tap A (24 VAC)

56 (17)

90 (27)

143 (43)

228 (69)

362 (110)

Tap B (26 VAC)

66 (20)

105 (32)

168 (51)

268 (81)

425 (129)

Tap C (28 VAC)

77 (23)

122 (37)

195 (59)

311 (94)

493 (150)

C561M-D (11/03)