Pentair CH installation manual Gas Connections, Gas Line Installations

Models: CH

1 36
Download 36 pages 27.89 Kb
Page 12
Image 12
GAS CONNECTIONS

Installation (contd.)

12

 

 

GAS CONNECTIONS

GAS LINE INSTALLATIONS

Before installing the gas line, be sure to check which gas the heater has been designed to burn. This is important because different types of gas require different gas pipe sizes. The rating plate on the heater will indicate which gas the heater is designed to burn. Tables 7-9, on pages 12 and 13, shows which size pipe is required for the distance from the gas meter to the heater. The table is for natural gas at a specific gravity of .65 and propane at specific gravity of 1.5.

When sizing gas lines, calculate three (3) additional feet of straight pipe for every elbow used.

When installing the gas line, avoid getting dirt, grease or other foreign material in the pipe as this may cause damage to the gas valve, which may result in heater failure.

The gas meter should be checked to make sure that it will supply enough gas to the heater and any other appliances that may be used on the same meter.

The gas line from the meter will usually be of a larger size than the gas valve supplied with the heater. Therefore a reduction of the connecting gas pipe will be necessary. Make this reduction as close to the heater as possible.

The heater and any other gas appliances must be disconnected from the gas supply piping system during any pressure testing on that system, (greater that ½ PSIG).

The heater and its gas connection must be leak tested before placing the heater in operation. Do not use flame to test the gas line. Use soapy water or another nonflammable method.

A manual main shut-off valve must be installed externally to the heater.

GAS LINE INSTALLATIONSWARNING

Do not install the gas line union inside the heater cabinet. This will void your warranty.

Pipe Sized For Length Of Run In Equivalent Feet

 

 

 

 

 

 

 

Table 7.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE SIZING FOR GAS LINE CONNECTIONS

 

 

 

 

 

 

 

 

MAXIMUM EQUIVALENT PIPE LENGTH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural gas at 1000 B.T.U. per Cubic Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Propane Gas at 2500 B.T.U. per Cubic Foot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2”

3/4”

1”

1-1/4”

1-1/2”

 

2”

2-1/2”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL

NAT

PRO

NAT

 

PRO

NAT

PRO

NAT

PRO

NAT

 

PRO

 

NAT

PRO

NAT

PRO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75 & 100

20’

50’

50’

 

150’

150’

600’

-

-

-

 

-

 

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

10’

40’

50’

 

150’

150’

600’

-

-

-

 

-

 

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

-

20’

30’

 

80’

125’

250’

450’

600’

-

 

-

 

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

-

10’

20’

 

50’

70’

150’

250’

500’

600’

 

-

 

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

-

-

10’

 

30’

50’

100’

200’

350’

400’

 

600’

 

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

350

-

-

10’

 

20’

30’

70’

125’

250’

250’

 

500’

 

500’

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

-

-

-

 

10’

20’

60’

100’

150’

200’

 

450’

 

400’

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

525

-

-

-

 

5’

15’

35’

65’

150’

130’

 

360’

 

390’

700’

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

750

-

-

-

 

-

-

20’

35’

80’

75’

 

180’

 

260’

600’

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

900

-

-

-

 

-

-

15’

20’

50’

45’

 

80’

 

150’

360’

400’

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P/N 472128