P/N 472032

INDOOR INSTALLATIONS

MINIMAX NT STANDARD VENTING GUIDELINES

Installation

vent terminated at least 24" above

any object within 10 ft.

10 ft.

Vent

Ridge

Cap

 

2 ft. min.

 

3 ft. min.

J

 

K

Detail H

L

Chimney

Vent for roof penetration installations:

Jmust extend at least 3 ft. higher than the point at which it passes through the roof, or as permitted by local code.

K must use a double-wall vent pipe through

the roof penetration.

H

E Air Supply

Ventilation

4'

Vent Hood

Air Supply

A Combustion

7'

F 1' min.

 

 

1' min.

 

Vent Hood

F

 

 

G

B

C

3'

4' D

 

 

 

 

1' min.

Vent Hood

 

above grade

G

(Indoor)

Rev

L must terminate with an approved (listed)

roof jack, storm collar, and vent/weather cap.

Vent pipe extension:

must be the same diameter as the vent connector.

must be suitable for use with category III appliances which have flue gas temperatures of less than 400 deg. F.

may use a single wall vent pipe with

Walkway

Recommended sources for

side wall Vent Hood; see page 15, Section Venting.

Vent termination for side wall installations:

Amust be not less than 7 ft. above public walkways.

Bmust be at least 3 ft. above any outside air intake located within a 10 ft. radius.

must NOT be within 3 ft. of an inside corner of the structure.

C must be at least 1 ft. above grade.

must be located the following distances away from any door, window, or gravity air inlet:

D4 ft. below

E4 ft. horizontally

F1 ft. above

. A

permanently sealed seams and joints.

Air Supply

Figure 16.

16

1-2-02

G See Air Supply Requirements Table.

(Table 2. on page 15.)

Page 16
Image 16
Pentair NT Standard Series installation manual Installation, Indoor