Philips Lighting Company | www.philips.com | Philips Lighting |
200 Franklin Square Drive |
| 281 Hillmount Road |
P.O.Box 6800 |
| Markham, Ontario |
Somerset, NJ |
| Canada L6C 2S3 |
| ||
A Division of Philips Electronics North America Corporation | A Division of Philips Electronics Ltd. | |
Updated 1/07 |
|
Ceramalux® High Pressure Sodium
Electrical Data (Subject to change without notice)
Lamp Watts (Nominal) | 200 |
|
Lamp Operating Voltage (rms) (Nominal) | 100V |
|
Initial Lamp Voltage Range (rms) |
| |
Lamp Operating Current (Amps) (rms) (Nominal) | 2.4 |
|
Maximum Lamp Starting Current (Amps)(rms) | 3.6 |
|
Lamp Current Crest Factor (Maximum) | 1.8 |
|
5 Minutes | ||
5 Minutes | ||
Ballast Type | ANSI S66 | |
Ballast Open Circuit Voltage (Minimum): | 198 Vrms | |
Pulse PeakVolts | 2225 |
|
Pulse Width @ 90% Peak | 1µs Minimum at 2250 Volts | |
Pulse Frequency (Minimum) |
|
|
Lag Ballast | 1 per Cycle | |
Lead Circuit Ballast | 1 per Cycle | |
Minimum Operating Temperature |
|
|
Reference Ballast Impedance | 74.6 | (ohms) minimum at 220V |
Maximum Lamp Watts | 260 Ω |
|
Minimum Lamp Watts | 140 |
|
Maximum Voltage Increase by Fixture | 10V |
|
|
|
|
Footnotes:
1)Measured at 100 hours of life in vertical and horizontal positions.
2)Approximate mean lumen output at 40% of lamp rated average life. Measured in vertical and horizontal operating positions.
3) Rated average life is the life obtained, on the average, from large representative groups of lamps in laboratory tests under controlled conditions at 10 or more operating hours per start. It is based on survival of at least 65% of the lamps and allows for individual lamps or groups of lamps to vary considerably from the average.
*The TCLP is the US EPA’s Toxicity Characteristic Leaching Procedure
WARNINGS, CAUTIONS AND OPERATING INSTRUCTIONS
for Ceramalux High Pressure SodiumLamps
R“WARNING:These lamps must be operated in fixtures designedfor use with High Pressure Sodium lamps.The fixture wattage rating must match the wattage
indicated on the outer glass bulb. Do not scratch the outer bulb or subject it to pressure as this could cause the outer bulb to crack or shatter. A partial vacuum in the outer bulb may cause glass to fly if the glass is struck. Operating the lamp improperly may result in
PERSONAL INJURY,PROPERTY DAMAGE,BURNS AND FIRE.
1)If the outer glass bulb is broken, shut off power immediately and remove the lamp after it has cooled.
2)Use only auxiliary equipment meeting Philips and/or ANSI standards. Use within voltage limits recommended by ballast manufacturer.
A.Operate lamp only within specified limits of operation.
B.For total supply load refer to ballast manufacturers electrical data.
3)Protect lamp base, socket and wiring against moisture, corrosive atmospheres and excessive heat.
4)Replace the lamp if the outer glass bulb has been scratched, cracked or damaged in any way.
5)If a lamp bulb support is used, be sure to insulate the support electrically so as to avoid possible decomposition of the bulb glass.
6)Do not use this lamp in a fixture which redirects a substantial portion of the energy toward the arc tube and its immediate vicinity,as this may lead to very early lamp failure.
7)Takecare in handling and disposing of lamps. If arc tube is broken, avoid skin contact with any of the contents or fragments.
8)The arc tube of this lamp contains sodium and mercury. Dispose of in accordance with federal, state and local requirements.