631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • A0508
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
MJ5 Exit Signs MJ5

Page 1 of 1 Chicago Exit Signs

Lightolier is a Philips group brand

Features
1. Illumi nation: AC Light Source: Standard exit face illumination is provided
by two 7 watt PL type fluorescent lamps. Letter brightness and illumination
uniformity exceed UL requirements with both incandescent and fluorescent
models. Emergency Light Source: Exit illumination in all models is provided by two
6 volt, 5.4 watt wedge base incandescent DC lamps. MJ5E-DEH combination
models with side mounted lighting heads are provided with 6 volt, 12 watt
halogen bi-pin lamps.
2. Housing: MJ5 Series exits are constructed of heavy duty steel finished
in white baked-on powder paint providing scratch and corrosion resistance.
Exit face features 6” letters with 3/4” stroke on translucent glass panels and
Full length directional arrows to meet City of Chicago visibility requirements.
Mounting canopy is standard.
3. Elec tronics: 120/277 VAC dual voltage inpu t with surge-p rotected,
solid-state circuitry. Full y automatic, tem perature comp ensating, variable rate
float charging system is complete wit h low voltage dis connect, AC loc kout,
brownout protect ion, AC indicator lam p and test swi tch.
4. Bat tery: Main tenance-free, s ealed, lead calcium b attery has an
estimated service life of 5 years, an d an operating t emperature r ange of 65°F
(19°C) to 85°F (30°C).
5. Inpu t Power Requir ements: AC Only: 19W; Emergenc y Operation: 29W
6. Warr anty: Unit : (excluding lamps) 3-y ears full cover age against defec ts
in materials and workma nship from date o f shipment. Bat tery: 3 yea rs full
warranty plus an addit ional 7 years of pro-rata co verage
Code Compliance
All models are UL Listed and meet NFPA 101 Life Safety Code, NEC, OSHA and City
of Chicago codes. Emergency models are UL924 Listed.
Options
DEH = Combination Model w/ Side Mounted Par 36 12W Halogen Heads
277 = 277VAC, 60Hz. Input (AC models only)
SW = Special Wording (consult factory)
SX = Self-Diagnostic Circuit (emergency models only)
IA = Audible Intermittent Alarm (emergency models only)
IV = Visual Intermittent Alarm (emergency models only)
FA = Fire Alarm Panel Interface
INC = Two candelabra base 15T6 120 volt, 15 watt incandescent AC lamps.
Accessories
MJSKW = 18” Stem Mounting Kit (white)
MJSKB = 18” Stem Mounting Kit (black)
MJPG9 = Wire Guard - Wall Mount (AC and emergency models)
MJPG10 = Wire Guard - Wall Mount (combination models)
Fluorescent or optional incandescent lamp AC-only and emergency exit models meet Chicago requirements. Rugged steel signs for wall, ceiling or end mount applications.
How to Specify:
MJ5
MJ5 =Chicago Exit
A B C D E 12.75” 9.5” 14.5” 2.5” 26.25” 32.4cm 24.1cm 36.8cm 6.4cm 66.7cm
SERI ES MODE OF # OF LETTER EXIT FACE
OPERATION FACES COLOR DESIGNATOR
Single Face Models
3 = EXIT (No Arrow)
6 = EXIT (Right Arrow)
9 = EXIT (Left Arrow)
12 = EXIT (Double Arrow)
2 = STAIRS (No Arrow)
5 = STAIRS (Right Arrow)
8 = STAIRS (Left Arrow)
11 = STAIRS (Double Arrow)
1 = Single face
2 = Double face
RW = Red on
White
Double Face Models
18 = EXIT (No Arrow)
21 = EXIT (Right or
24 = EXIT (Double Arrow)
17 = STAIRS (No Arrow)
20 = STAIRS (Right or
Left Arrow)
23 = STAIRS (Double
Arrow)
RW
A = AC Only Exit
E = Emergency
Operation Exit
Standard Exit Combination Model (DEH option)