To unlock the control panel:
1.Press and hold the UP and DOWN buttons simultaneously for 10 seconds.
2.Pon flashes on the display and the keyboard is unlocked.
Note:
If a button is not pressed for 10 seconds while using the control panel it times out and reverts to standby mode.
When parameters are being set the Setpoint LED will flash on the display.
Enter the Parameter Menu
1.Unlock the control panel, if locked.
2.Press and hold the SET button until ‘d1’ flashes on the display.
3.Press the SET button repeatedly to scroll to the desired parameter (see below).
.
Parameter | Name |
|
| Description | Range | |
|
|
|
|
|
| |
d1 | Operating temperature | Set the operating temperature of the appliance | ||||
|
|
|
|
|
| |
d2 | Temperature | The Temperature Differential is the allowed temperature difference above and below the | 0 to 20°C | |||
Differential | operating temperature before the compressor starts/cuts off | |||||
|
| |||||
|
|
|
|
|
| |
d3 | Temperature Range | Set the minimum (d3) and maximum (d4) temperatures that the appliance can fluctuate | ||||
|
| |||||
| between |
| ||||
d4 | 95°C | |||||
| ||||||
|
|
|
| |||
|
|
|
|
|
| |
d5 | Compressor Activation | Enter the minimum time interval between the compressor turning off after turning on. | ||||
Time Intervals | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
d6 | Maximum Temperature | Set an alarm to sound if the temperature inside the appliance exceeds the set operating | ||||
Differential Alarm | temperature by a specified amount | |||||
|
| |||||
|
|
|
|
|
| |
d7 | Temperature | Set a delay before the temperature differential alarm is triggered | ||||
Differential Alarm Delay | ||||||
|
|
|
|
|
| |
d8 | Defrost Cycle Time | Set the time between each defrost cycle | ||||
Intervals | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
| Maximum Defrost | Set the maximum length of the defrost cycle |
| |||
d9 | Note: The defrost duration can be overridden by parameter d10 (below), if the | |||||
Duration | ||||||
|
| |||||
|
|
| ||||
|
|
|
|
|
| |
d10 | Defrost | Set the defrost | ||||
Temperature | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
d11 | Additional | Set an additional amount of defrost time after the defrost | ||||
Defrost Period | required) | |||||
|
|
|
|
|
| |
d12 | Delayed Actual | Set the length of time the inner temperature of the appliance (before defrost started) is | ||||
Temperature Display | displayed for after a defrost cycle has finished | |||||
|
| |||||
|
|
|
|
|
| |
d13 | Compressor On/Off | Turn the Compressor On or Off during the defrost cycle | On (1) or Off (0) | |||
During Defrost | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
d14 | Evaporator Drying Time | Set the amount of time the compressor remains turned Off after a defrost cycle, reducing the | ||||
amount of frost build up | ||||||
|
|
| ||||
|
|
|
|
|
| |
=19 | Temperature Offset | Should there be any variance between measured and actual temperature, the measured | ||||
temperature can be offset to compensate | ||||||
|
|
| ||||
|
|
|
|
|
| |
=22 | Unit of Measurement | Set whether the temperature is displayed in Centigrade or Fahrenheit | Centigrade (0) or Fahrenheit (1) | |||
|
|
|
|
|
| |
| Compressor Operation |
|
|
| Compressor runs (1) | |
=23 | Set whether the compressor runs or remains Off during a temperature probe failure | Remains Off until fault fixed (0) | ||||
During Probe Failure | Runs intermittently with | |||||
|
|
|
| |||
|
|
|
|
| parameters =24 and =25 (2) | |
|
|
|
|
|
| |
=24 | Compressor ‘On’ | Set the length of time the compressor runs during a temperature probe failure | ||||
Duration | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
=25 | Compressor ‘Off’ | Set the length of time the compressor remains Off during a temperature probe failure | ||||
Duration | ||||||
|
|
|
|
| ||
|
|
|
|
|
| |
=34 | Initial Defrost After | Set whether the appliance starts a defrost cycle 10 minutes after startup or after the time | Begins 10 minutes after startup | |||
Startup | programmed in parameter d8 (Defrost Cycle Time Intervals) | (0) or when programmed (1) | ||||
| ||||||
|
|
|
|
|
| |
=38 | Minimum Temperature | Set the display to flash should the inner temperature of the appliance drop beyond a specified | 1°C to 50°C | |||
Alarm | point from the programmed operating temperature | |||||
|
| |||||
|
|
|
|
|
|
Manual Defrost
The appliance will automatically run a defrost cycle every six hours.
Note: The cycle starts from the time the appliance is initially powered up.
To manually defrost the appliance:
1.Press and hold the DEFROST button for 5 seconds.
2.The defrost cycle will start immediately and the Defrost LED illuminates. The defrost will last a maximum of 30 minutes.
Note: Starting a manual defrost also resets the automatic defrost timer.
3.The next automatic defrost will start six hours after the manual defrost has finished.
2