Powerware® 5140 Model Selection Guide

 

MO D E L

PO W E R OU T

IN P U T /O U T P U T

FR E Q U E N C Y

IN P U T

OU T P U T

DI M E N S I O N S

WE I G H T

 

NU M B E R

(VA/WAT T )

VO LTA G E (VA C )

(H Z )

C O N N E C T I O N

RE C E P TA C L E S

(HX WX D) 1

(K G /L B )

 

 

 

 

 

 

(12) IEC-320, C13 &

10.5 x 17.25 x 24.3 in

 

 

PW5140 6000i

6000/6000

208/2302

50/603

Hardwired

(3) IEC-320, C194

26.7 x 43.8 x 61.7 cm

136/3006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2) L6-30R &

10.5 x 17.25 x 24.3 in

 

 

PW5140 6000

6000/6000

208/2302

50/603

Hardwired

(2) IEC-3205

26.7 x 43.8 x 61.7 cm

136/3006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hardwired &

10.5 x 17.25 x 24.3 in

 

 

PW5140 6000 HW

6000/6000

208/2302

50/603

Hardwired

(2) IEC-3205

26.7 x 43.8 x 61.7 cm

136/3006

 

Options

 

 

 

 

 

 

 

 

 

 

 

 

Custom

 

5.25 x 17.25 x 22.5 in

 

 

PW5140 BATT

Adapter

13.3 x 43.8 x 57.2 cm

81.6/180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Custom

 

1.98 x 19.28 x 9.90 in

 

 

PW5140 PDU7

250/250

120

60

Adapter

(2) 5-15R

5.03 x 48.97 x 25.15 cm

8.6/19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjustable; fits

 

 

PW5119 MK23

standard 19-inch rack

4.5/10

1.19-inch wide front panel with a 17.25-inch wide chassis; depth does not include front panel (.5 inches) 2. 208/230 Vac auto-sensing default. User-selectable via LCD interface for 200, 208, 220, 230, and 240 Vac. 3. Automatic frequency synchronization. 4. Divided into 5 Load Segments. 5. Divided into 2 Load Segments; IEC-320 receptacles are used to connect optional PW5140 PDU. 6. Shipping weight is 325 pounds (147 kg). 7. Sidewall design occupies 0U of rack space.

B AT T E R Y R U N T I M E S

 

 

STA N D A R D

ON E AD D I T I O N A L

TW O AD D I T I O N A L

 

LO A D

BAT T E R I E S

EX T E N D E D BAT T E R Y MO D U L E

EX T E N D E D BAT T E R Y MO D U L E S

 

1000 Watts

1 hour 2 minutes

2 hours 24 minutes

3 hours 56 minutes

 

 

 

 

 

 

 

2000 Watts

28 minutes

1 hour 6 minutes

1 hour 47 minutes

 

 

 

 

 

 

 

3000 Watts

18 minutes

40 minutes

1 hour 6 minutes

 

 

 

 

 

 

 

4000 Watts

12 minutes

28 minutes

47 minutes

 

 

 

 

 

 

 

5000 Watts

8 minutes

21 minutes

36 minutes

 

 

 

 

 

 

 

6000 Watts

6 minutes

18 minutes

28 minutes

This table provides typical information. Battery times are approximate and may vary with equipment, configuration, disk access, battery use, temperature, etc.

R E A R PA N E L S

PW5140 6000i

A(2) IN S TA L L A B L E OP T I O N SL O T S

B(2) CO M M U N I C AT I O N PO R T S

CMA N U A L BY PA S S SW I T C H

DREPO PO R T

PW5140 6000

EHA R D W I R E IN P U T

FLO A D S E G M E N T 1

GLO A D S E G M E N T 2

HLO A D S E G M E N T 3

PW5140 6000 HW

ILO A D SE G M E N T 4

JLO A D SE G M E N T 5

KCI R C U I T BR E A K E R (S )

LIEC-320 RE C E P TA C L E S F O R PDU CO N N E C T I O N

MHA R D W I R E OU T P U T

Powerware Corporation

Latin America/Caribbean

China and North Asia

Corporate Headquarters

Sunrise, FL: 954.835.1180

Hong Kong: 852.2745.6682

8609 Six Forks Road

Europe/Middle East/Africa

Australia and South Pacific

Raleigh, NC 27615 U.S.A.

Berkshire, England: 44.1753.606700

Sydney, Australia: 61.2.9878.5000

Toll Free: 1.877.797.9273 (PWRWARE)

 

 

or 919.872.3020

Southeast Asia

Canada

Fax: 1.800.753.9433

Singapore: 65.861.9877

Toronto, Ontario: 416.798.0112

or 919.870.3411

 

 

E-mail: info@powerware.com

 

 

www.powerware.com

 

 

Revision 5140FXA 7/99 Reprint 7/99

Page 4
Image 4
Powerware warranty Powerware 5140 Model Selection Guide, Options, Repo PO R T