Powerware 9170+ manual Shut down function, Relay information available, Shut down options

Models: 9170+

1 2
Download 2 pages 62.02 Kb
Page 2
Image 2

Table 1. Relay information available.

Relay #

System state

D15 pin #

NC / NO *

on board

 

connected

 

K1: Line

Line OK

1 - 2

NC

 

Line failure

1 - 3

NO

K2: Battery

Battery normal

4 - 5

NC

 

Battery low

4 - 6

NO

K3: UPS Alarm

UPS alarm

7 - 8

NC

 

UPS ON / OK

7 - 9

NO

K4: Bypass

UPS on bypass

10 - 12

NC

 

UPS normal / On inverter

10 - 11

NO

 

UPS shutdown **

13 - 15

 

Table 1

*Normally closed (NC) /open (NO) connection state when the Relay Interface Card is not powered.

**The shutdown pin (15) needs minimum of 5 seconds high level signal (connection to +12VDC) to perform the UPS shutdown.

NOTICE: The relay contacts must not be galvanically connected to any mains connected circuits. Do not use +12VCD (Pin13) of the Relay Interface Card for any power supply purposes for external devices. Reinforced insulation to the mains is required for equipment and cables connected to these connections.

The relay contacts are rated for maximum 1A/30VAC or 200mA/60VDC. All relay outputs are galvanically isolated from the other circuits of the UPS (IEC 950, EN 50091-1).

Shut down function

The Relay Interface Card shut down functionality depends on the jumper (JP1, JP2 & JP3) selected on the board and on the UPS mode (Normal or On Battery). The functions are described in table 2.

Table 2. Shut down options.

 

 

JP1 (factory default)

JP2

JP3

PW

UPS

-

-

-

9110

Normal

 

 

 

 

On Battery

-

UPS Off immediately, back

-

 

 

 

online when power returns.

 

PW

UPS

-

Immediate output off, back

Immediate output off

9120

Normal

 

on line when shut down

 

 

 

 

pins are opened

 

 

On Battery

Shut down as in RS-232

Immediate output off, back

Immediate output off

 

 

port. Output off after 120

on line when shut down

 

 

 

sec, back on line when

pins are opened

 

 

 

power returns.

 

 

PW

UPS

-

-

Immediate output off

9170+

Normal

 

 

 

 

On Battery

-

Immediate output off

Immediate output off

Table 2

1018946 Rev. A

2/2

Page 2
Image 2
Powerware 9170+ manual Shut down function, Relay information available, Shut down options