![](/images/new-backgrounds/1108754/10875441x1.webp)
TIE CABINET INSTALLATION
22.Wire the maintenance bypass auxiliary contacts and terminate to the maintenance bypass wires in the Tie Cabinet (see Figure 6 on page 12).
Connect the black and the red wire to TB4 on the UPS (see Figure 9). Cap the blue wire.
NOTE The maintenance bypass contacts are
NOTE There are two sets of maintenance bypass wires; you can terminate to either set. If you are installing four UPSs, it is recommended to terminate two UPSs to one set of wires and two UPSs to the other set of wires.
| Red Wires | |
| (open when breaker is open) | |
350A Breaker | Black Wires | |
(common) | ||
Auxiliary Contacts | ||
| ||
| Blue Wires | |
350A | (closed when breaker is open) |
Bypass Input |
|
110A (4X) | LOAD |
From UPS 1 Output |
|
From UPS 2 Output |
|
From UPS 3 Output |
|
From UPS 4 Output |
|
Figure 9. Parallel Wiring Diagram
23.Reinstall the UPS wiring access cover.
24.Reinstall the UPS conduit landing box in the reversed position.
EATON Powerware® 9355 Tie Cabinet (20/30 kVA) Installation Guide S 164201630 Rev A www.powerware.com | 15 |