Product Options

The PrecisionCell M16 filters are available as gasket seal only, contact factory for additional options.

Gasket Seal

The standard filter gasket is 1/4” black poly- butyl attached to the frame with a pressure sensitive adhesive. Other gasket options are available upon request.

Faceguards

The standard filter faceguard is an expanded galvanized screen on the downstream side. Other materials and locations are available upon request.

PrecisionCell M16 Selection

All products have a rated overall DOP efficiency of 92% at 0.3µm and are rated MERV 16 per ASHRAE standard 52.2.

Filter model number breakdown.

0 - 00T - W - 16 - 00 - IU - B2 - 00 - YY- F

Filter Frame Material:

Use “16” for galvanized, “05” for aluminum,

and “03” for stainless steel.

Filter Frame Style:

Use “00” for box style, “01” for single header, “02” for double header, and “03” for double turn flange style.

Faceguard style and location Use “00” for none, “G1” for expanded galvanized upstream,

“G2” for expanded galvanized downstream “G3” for expanded galvanized both sides.

Gasket Style and Location: Use “00” for none, “B1” for black poly-b upstream,

“B2” for black poly-b downstream, and “B3” for black poly-b on both sides.

Filter Size:

Filter Size Designator

Filter Height

Filter Width

Filter Depth

Rated Airflow

 

YY-F

23-3/8”

23-3/8”

11-1/2”

2000 CFM

 

YU-F

23-3/8”

11-3/8”

11-1/2”

1000 CFM

 

YX-F

23-3/8”

19-3/8”

11-1/2”

1700 CFM

 

XX-F

19-3/8”

19-3/8”

11-1/2”

1400 CFM

 

ZX-F

24-3/8”

19-3/8”

11-1/2”

1750 CFM

®

Flanders Filters, Inc.

531 Flanders Filter Road Washington, NC 27889

Phone: (252) 946-8081

Fax: (252) 946-3425

Toll Free: (800) 637-2803

Website: www.flanderscorp.com