LOW NOx MAXIM • PACKAGED GAS WATER HEATER

POLYSHIELD® POLYMER-LINED STORAGE TANK

125 GALLON TANK SERIES

 

MODEL NUMBER

20 P 125A-MXS

27 P 125A-MXS

40 P 125A-MXS

 

GPH Recovery at 40° to 120° F

245

330

490

 

GPH Recovery at 40° to 140° F

195

260

390

 

Input Btu/h

199,000

270,000

399,000

 

Minimum gas inlet pressure – " W.C.

5.5

5.5

5.5

A

Cold Inlet - NPT

2

2

2

B

Hot Outlet - NPT

2

2

2

C

Drain - NPT

1

1

1

D

I - Beam Skids

3 X 34-1/2

3 x 34-1/2

3 x 34-1/2

E

Overall Depth

45

45

45

F

Overall Height

75

75

82

G

Flue Outlet Diameter

5

6

7

H

Gas Inlet - NPT

1/2

3/4

3/4

J

Motor HP 120 V, 1Ø, 60 Hz.

1/6

1/6

1/6

 

Motor Amps

1.75

1.75

1.75

L

Height to Outlet

65

65

73

M

Height to Inlet

28

28

36

 

Approx. Shipping Weight - lbs

1020

1070

1130

Recoveries based on 82% thermal efficiency. ASHRAE 90.1 compliant. Dimensions are in inches unless otherwise specified.

For standard and optional equipment, see Form # PV6377.

1.Control Enclosure

2.ASME Temperature & Pressure Relief Valve

3.3” NPT Handhole

STANDARD GAS PRESSURE REQUIREMENTS:

SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.

MAXIMUM STATIC PRESSURE: 9" W.C.

FOR GAS PRESSURES OUTSIDE OF THIS RANGE,

CONTACT YOUR PVI REPRESENTATIVE.

STANDARD ELECTRICAL REQUIREMENTS:

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS

VENTING REQUIREMENTS:

-.02" TO -.06" W.C. (NEGATIVE PRESSURE).

TYPE B VENTING.

THE ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE

VENT CONNECTION DIAMETER EXCLUSIVELY.

FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL GAS CODE

UNDER "FAN-ASSISTED".

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND SPECIFICATION WITHOUT NOTICE.

Product is patented in the U.S., Canada, and Mexico.

 

PVI INDUSTRIES, LLC

PV 6378 02/05

FORT WORTH, TEXAS 76111

(800) 784-8326 • www.pvi.com