F-4

TROUBLESHOOTING & REPAIR

 

 

 

F-4

 

 

 

Observe Safety Guidelines

 

TROUBLESHOOTING GUIDE

detailed in the beginning of this manual.

 

 

 

 

 

PROBLEMS

 

POSSIBLE AREAS OF

RECOMMENDED

 

(SYMPTOMS)

 

MISADJUSTMENT(S)

COURSE OF ACTION

 

 

 

 

 

 

 

 

 

 

OUTPUT PROBLEMS

 

 

 

 

 

Major Physical or

Electrical

1. Contact your local Lincoln

1. Contact The Lincoln Electric

Damage is Evident.

 

Authorized Field Service

Service Dept. 1-888-935-3877.

 

 

Facility.

 

 

 

 

 

 

 

 

No weld output and no auxiliary

1. Check the brushes for wear and

1. Perform the Rotor Voltage

power. Engine runs normally.

proper contact to the rotor slip

Test.

 

 

 

 

 

 

rings.

2. Check for the presence of

 

 

 

 

 

 

12VDC (at the pc board) from

 

 

 

lead #216 to frame ground.

 

 

 

This is the “flashing” voltage

 

 

 

and is present only when the

 

 

 

Start, Run, Stop switch S3 is in

 

 

 

the “Start” position. If the 12

 

 

 

VDC is missing check the leads,

 

 

 

switches

and

connections

 

 

 

associated with the lead #216.

 

 

 

See Wiring Diagram.

 

 

 

 

Check for the presence of 12

 

 

 

VDC (at the pc board) from lead

 

 

 

#224 to frame ground. This is

 

 

 

the supply voltage to the board

 

 

 

and is present when the engine

 

 

 

is running and the S3 switch is

 

 

 

in the “Run” position. If the

 

 

 

12VDC is missing check the

 

 

 

leads, switches and connec-

 

 

 

tions associated with the lead

 

 

 

#224. See Wiring Diagram.

 

 

 

3. If Rotor Voltage Test is normal,

 

 

 

then

preform

the

Rotor

 

 

 

Resistance Test.

 

 

 

 

 

4. If the Rotor Voltage Test is NOT

 

 

 

normal, perform

the Auxiliary

 

 

 

and

Field

Winding

Voltage

 

 

 

Test. Then check the Field

 

 

 

Diode Bridge (D2) and the Field

 

 

 

Capacitor (C1). Replace if nec-

 

 

 

essary. If the Field Bridge and

 

 

 

Field Capacitor are good, then

 

 

 

the Printed Circuit Board may

 

 

 

be faulty. Replace.

 

CAUTION

If for any reason you do not understand the test procedures or are unable to perform the test/repairs safely, con- tact the Lincoln Electric Service Department for electrical troubleshooting assistance before you proceed. Call 1-888-935-3877.

RANGER® 10,000 & RANGER® 10,000 PLUS

Page 44
Image 44
Lincoln Electric SVM168-B service manual Troubleshooting Guide, Output Problems