TURBOPOWER® OIL

PACKAGED WATER HEATER

 

 

 

 

NICKELSHIELD® NICKEL-PLATED STORAGE TANK

 

 

 

 

 

 

 

 

TANK SERIES 225 GALLONS

 

 

 

 

 

 

Recovery gph

 

 

Dimensions

 

Blower

Shipping

Model

Input

Gph

 

(inches)

 

 

Motor

 

 

 

 

 

 

 

Weight

Number

 

 

 

 

Btu/h

#2 Oil

 

 

 

 

 

 

 

40°- 120°F

40°- 140°F

A

 

B

 

J

HP

Volt/Ph/Amps

lbs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

N 225A-TPO

250

 

200

199,000

1.4

28

 

4

 

17

1/3

115/1/8

1380

500

N 225A-TPO

500

 

400

399,000

2.8

28

 

5

 

17

1/2

115/1/10

1400

750

N 225A-TPO

750

 

600

600,000

4.3

42

 

6

 

17

1/2

115/1/10

1480

1000

N 225A-TPO

1000

 

800

800,000

5.7

42

 

8

 

17

1/2

115/1/10

1520

Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss. "J" dimension is for the burner housing only.

Dimensions are in inches unless otherwise specified. For standard and optional equipment, see form PV 6004.

VENTING REQUIREMENTS

-.02" TO -.06" W.C. (NEGATIVE PRESSURE)

ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.

FOR PROPER SIZING, CONSULT VENTING SUPPLIER.

STANDARD ELECTRICAL REQUIREMENTS

CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS.

MOTOR VOLTAGE:

208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR AN OPTIONAL CONTROL CIRCUIT TRANSFORMER.

PVI RESERVES THE RIGHT TO CHANGE THE DESIGN AND SPECIFICATION WITHOUT NOTICE.

PVI INDUSTRIES, LLC

FORT WORTH, TEXAS 76111

PV 5359 04/05

(800) 784-8326 (817) 335-9531 www.pvi.com

Product is patented in the U.S., Canada, and Mexico.

 

 

Page 1
Image 1
PVI Industries 500 N 225A-TPO, 750 N 225A-TPO dimensions Turbopower OIL Packaged Water Heater, Venting Requirements