| TURBOPOWER→ GAS/OIL | PACKAGED WATER HEATER |
|
|
| ||||||||||||
|
|
|
| POLYSHIELD→ |
|
|
|
|
| |||||||||
|
|
|
|
|
| TANK SERIES 125 GALLONS |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| HORIZONTAL |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Recovery gph |
| Min. Inlet Flow |
| Dimensions (inches) |
| Blower | Shipping | ||||||||
| Model |
| Input | #2 Oil |
| Motor | ||||||||||||
| Number |
|
|
|
| Btu/h | Gas Pressure | gph |
|
|
|
|
|
|
|
| Weight | |
|
|
|
|
|
|
|
|
|
|
|
| Volt/Ph/ | ||||||
|
| 40°- 120°F | 40°- 140°F | "W.C. | A | B | C | J | HP |
| lbs | |||||||
|
|
|
|
|
| Amps | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
750 | PHE |
| 750 | 600 |
| 600,000 |
| 4.5 | 4.3 | 42 | 6 | 1 | 31 | 1/2 |
| 115/1∅/10 | 1420 | |
1000 | PHE |
| 1000 | 800 |
| 800,000 |
| 6.0 | 5.7 | 42 | 8 | 1 | 31 | 1/2 |
| 115/1∅/10 | 1460 | |
1250 | PHE |
| 1250 | 1000 |
| 1,000,000 |
| 7.5 | 7.2 | 42 | 8 | 1 | 31 | 3/4 |
| 115/1∅/14 | 1550 | |
1500 | PHE |
| 1500 | 1200 |
| 1,200,000 |
| 7.5 | 8.6 | 42 | 8 | 31 | 1 |
| 115/1∅/16 | 1630 |
Recoveries based on 83% thermal efficiency. ASHRAE 90.1 compliant for efficiency and standby loss. “J” dimension is for the burner housing only. Gas train may exceed this dimension.
Standard gas train.
*The information presented is for Natural gas 0.6 S.G.— For operation with propane (LP gas), consult factory. Dimensions are in inches unless otherwise specified.
Burner control panel requires 18" clearance for door swing. For standard and optional equipment, see form PV 6047.
*GAS PRESSURE REQUIREMENTS
SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER.
MAXIMUM STATIC INLET PRESSURE: 14" W.C.
FOR PRESSURES OTHER THAN LISTED, CONSULT FACTORY.
Pressure shown is for standard UL gas train. Additional controls
may increase pressure requirements.
VENTING REQUIREMENTS
-.02" TO -.06" W.C. (NEGATIVE PRESSURE)
ENTIRE VENT SYSTEM SHOULD NEVER BE SIZED BASED UPON THE VENT CONNECTION DIAMETER EXCLUSIVELY.
FOR PROPER SIZING, CONSULT
THE NATIONAL FUEL GAS CODE UNDER
* REAR ACCESS MODULE
MODEL PREFIX | M | L | STD or OPTIONAL |
|
|
|
|
23" | N/A | OPTIONAL | |
|
|
|
|
|
|
|
|
STANDARD ELECTRICAL REQUIREMENTS
CONTROL VOLTAGE: 120V, 1Ø, 60 HZ., 2 AMPS.
MOTOR VOLTAGE:
208V, 230V, AND 460V MOTORS ARE AVAILABLE BUT WILL REQUIRE A SEPARATE 120V/2 amps CONTROL CIRCUIT OR AN OPTIONAL CONTROL CIRCUIT TRANSFORMER.
PVI RESERVES THE RIGHT TO CHANGE THE DESIGN
AND SPECIFICATION WITHOUT NOTICE.
PVI INDUSTRIES, LLC
FORT WORTH, TEXAS 76111
PV 5477 02/04 | (800) | Product is patented in the U.S., Canada, and Mexico. |
|
|