SPECIFICATION FOR DOMESTIC WATER HEATERS

Power Combustion, Oil-Fired Water Heaters with Nickel-Plated Storage Tanks

Furnish and install TURBOPOWER® oil water heater(s) as manufactured by PVI INDUSTRIES, INC of Fort Worth, Texas. Supply quantities and model numbers as indicated on the plumbing schedule.

Efficiency

The water heater will operate at a minimum of 83% thermal efficiency. The water heater will comply with paragraph 7.2.4.4, the thermal efficiency, the standby loss, and all other requirements of ASHRAE 90.1-1999.

Pressure Vessel and Heating Surfaces

The water heater will be constructed and stamped in accordance with Section IV, Part HLW of the ASME code.

The storage section of the water heater will be National Board Registered for a working pressure of ____ 125 psi

(standard) or ____ 150 psi and will be pressure tested at 1-1/2 times working pressure. The heating section of the water

heater will be National Board Registered for a working pressure of 150 psi and will be pressure tested at 1-1/2 times working pressure.

The heat exchanger will be a firetube design with the combustion chamber and all heating surfaces completely water-backed. The fireside of the combustion chamber will be of boiler-grade steel. The waterside of the combustion chamber will be non-ferrous. The fire tubes will be solid copper. The heating surfaces will be removable by unbolting from the pressure vessel, allowing 100% access to waterside surfaces. The tank will be accessible in the field through a manway sized opening, allowing access to 100% of interior surfaces. All tank connection fittings will be nonferrous and removable from the tank.

Tank Lining

The tank will be a plated with electroless nickel (EN). Plating will occur after the pressure vessel is completely fabricated and all welding is completed. The EN plating will be a high-phosphorus (10%) and nonporous composition suitable for submersion service (ASTM B733 standard may be used as a guideline). For additional protection against galvanic corrosion, which may occur within the potable water system, the electroless nickel plating may have a high- dielectric-strength polymer overcoat.

The lined tank will not require sacrificial anode rods and none will be used. Water heaters that use anode rods in a vessel that contains non-ferrous heating surfaces will not be acceptable.

Burner and Venting

Combustion will be provided by a forced-draft power burner with an oil train meeting the following agency requirement for the input specified:

___ UL (standard) ___ FM ___ IRI ___ Other ______________________

Burner will be configured to accept ____ room air _____ direct inlet combustion air.

(continued)

PV 6112b 6/03

1

Page 1
Image 1
PVI Industries PV 6112b manual Specification For Domestic Water Heaters, Efficiency, Pressure Vessel and Heating Surfaces

FAQ

What is the minimum thermal efficiency of the water heater?

The water heater will operate at a minimum of 83% thermal efficiency.

What are the pressure vessel and heating surfaces constructed and stamped in accordance with?

The water heater will be constructed and stamped in accordance with Section IV,Part HLW of the ASME code.

What type of burner provides combustion for the water heater?

Combustion will be provided by a forced-draft power burner with an oil train.