Raypak 0133-4001 manual Vent Piping

Models: 0133-4001

1 53
Download 53 pages 53.15 Kb
Page 14
Image 14
VENT PIPING

VENT PIPING

WARNING: Indoor heaters require a drafthood that must be connected to a vent pipe and properly vented to the outside. Failure to follow this procedure can cause fire or fatal carbon monoxide poisoning.

Vent piping of the same size as the drafthood outlet is recommended, however, when the total vent height is at least ten (10) feet (drafthood relief opening to vent terminal), the vent pipe size may be reduced as speci- fied in the National Fuel Gas Code, ANSI Z 223.1. Avoid long horizontal runs of vent pipe and too many elbows. If installation requires horizontal non- vertical runs, the vent pipe must have a minimum of

1/4 inch per foot rise and should be supported at not more than five foot intervals. Plumber's tape, criss- crossed, will serve to space both horizontal and vertical piping. Gas vents supported only by the flashing and extending above the roof more than five feet should be securely guyed or braced to withstand snow and wind loads. We recommend use of an insulated vent pipe spacer through the roofs and walls.

For protection against rain or blockage by snow, the vent pipe must terminate with a vent cap which com- plies with the local codes or, in the absence of such codes, to the latest edition of the National Fuel Gas Code, ANSI Z223.1.

The discharge opening must be a minimum of two feet vertically from the roof surface and at least 2 feet higher than any part of the building or equipment within ten feet. The vent stack shall be at least 5 feet in vertical height above the drafthood outlet. The vent cap loca- tion shall have a minimum clearance of 4 feet horizon- tally from, and in no case above or below, unless a 4- foot horizontal distance is maintained, from electric meters, gas meters regulators and relief equipment.

.

Manual background 10' OR LESS

Manual backgroundVENT CAP

2' MIN

2' MIN

5' MIN

VENT PIPE Manual background

DRAFT HOOD Manual background

HEATER Manual background

The weight of the vent stack or chimney must not rest on heater drafthood. Support must be provided in compliance with applicable codes. The heater top and drafthood must be readily removable for maintenance and inspection. Vent pipe should be adequately sup- ported to maintain proper clearances from combustible construction Type "B" double wall or equivalent vent pipe is recommended. However single wall metal vent pipe may be used as specified in the latest edition of the National Flue Gas Code ANSI Z223.1.

Manifolds that connect more than one heater to a common chimney must be sized to handle the com- bined load. Consult available guides for proper sizing of the manifold and the chimney. At no time should the area be less than the area of the largest outlet.

Fig. #7043.1

At the time of removal of an existing heater, the follow- ing steps shall be followed with each appliance remain- ing connected to the common venting system placed in operation, while the other appliances remaining con- nected to the common venting system are not in operation.

(a)Seal any unused openings in the common venting system.

(b)Visually inspect the venting system for proper size and horizontal pitch and make sure there is no blockage or restriction, leakage, corrosion or other deficiency which could cause an unsafe condition.

(c)Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the com- mon venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will oper- ate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

14

Page 14
Image 14
Raypak 0133-4001 manual Vent Piping