Raypak 055B installation instructions

Models: 055B

1 32
Download 32 pages 6.93 Kb
Page 10
Image 10
HIGH WIND CONDITIONS (OUTDOOR UNITS ONLY) In areas where high winds are frequent, it may be necessary to locate the heater a minimum of 3' from high vertical walls, or install a wind break so the heater

HIGH WIND CONDITIONS (OUTDOOR UNITS ONLY) In areas where high winds are frequent, it may be necessary to locate the heater a minimum of 3' from high vertical walls, or install a wind break so the heater

is not in direct wind current.

INDOOR HEATERS

The design is also certified for indoor installation when equipped with the approved draft hood. For Canada, indoor installation is restricted to an enclosure that is not occupied and does not directly communicate with occupied area. Refer to the latest edition of CAN/ CGA-B149.1 and B149.2 for specific requirements.Locate heater as close as practical to a chimney or gas vent. Heater must always be vented to the outside. See Vent Piping Section for venting details. Minimum allowable space is shown on the nameplate.

Heater with

Indoor Top

VENTING CONNECTIONS

VENT TERMINAL (Outdoor)

STEP

1: Remove the (4) screws which fasten

 

jacket top to heater.

STEP

2: Lower outdoor top onto unit lining up

 

slots in outdoor top with screw holes in

 

jacket top.

STEP

3: Reinstall (4) screws to secure jacket top

 

and outdoor top to unit.

Outdoor Top

Jacket Top

Fig. # 8138

Fig. # 8137

COMBUSTION AIR (INDOOR UNITS ONLY) Air For combustion And Ventilation

(Indoor Units Only)

The heater must have both combustion and venti- lation air. Minimum requirements for net free air supply openings, one 12 inches from ceiling for ventilation and one 12 inches from the floor for combustion air as outlined in the latest edition ofthe National Fuel Gas Code, Z223.1(Canada-CAN/CGA-B149.1 and B149.2) and any local codes that may have jurisdiction.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty.

a.All Air From Inside The Building:

Each opening shall have a minimum of 50 net free square inches.

b.All Air From Outdoors:

When air is supplied directly from outside of building, each opening shall have a minimum of 13 net free square inches.

VENT TERMINAL (Indoor)

Locate and assemble as shown. Secure with screws supplied in envelope inside carton.

Draft Hood

Mounting

Screws

Fig. # 8143

9

Page 10
Image 10
Raypak 055B installation instructions