Raypak 055B installation instructions U.S. Installation Only

Models: 055B

1 32
Download 32 pages 6.93 Kb
Page 9
Image 9
U.S. Installation Only

ALL HEATERS

For clearances from combustible surfaces, see chart below.

Clearances from Combustible construction. Indoor Installation:

Top* (Drafthood) - 35"; Vent - 6"; Back - 2"; Right Side - 6";

Left Side - 6"; Floor - 0. Outdoor Installation:

Top* (Stackless Top) - unobstructed; Back - 2"; Sides - 6".

* Clearance from Top of Vent Terminal

For servicing, provide at least 24" in front of the heater for burner tray removal, and at least 18" on the left side of the heater to inspect and delime the heat exchanger.

OUTDOOR HEATERS

These heaters are design certified for outdoor installation, when equipped with the approved top des- ignated for outdoor use.

Heater with outdoor Top

Fig. # 8139

WARNING: Do not install within 3 feet of a Heat Pump or an outdoor condensing unit. Strong air intake from these equipment can disturb the combustion process and cause damage or personal injury.

Heaters must not be installed under an overhang of less than three (3) feet from the top of the heater. Three

(3)sides must be open in the area under the overhang. Roof water drainage must be diverted away from the heaters installed under overhangs with the use of gutters:

For U.S. installations, the point from where the flue products exit the heater must be a minimum of four (4) feet below, four (4) feet horizontally from or one (1) foot above any door, window or gravity inlet to a building. The top surface of the heater shall be at least three (3) feet above any forced air inlet, or intake ducts located within ten (10) feet horizontally.

For installations in Canada, pool heaters shall not be installed with the top of the vent assembly within 10 feet below, or to either side, of any opening into the building. Refer to the latest revision of CAN/CGA-B149.1 and B149.2.

4 foot

 

Minimum

 

 

4 foot

 

Minimum

4 foot

 

Minimum

 

3 foot

 

Minimum

 

10 foot

1 foot

Minimum

Minimum

 

Forced Air Inlet

 

U.S. Installation Only

Fig # 8245.1

8

Page 9
Image 9
Raypak 055B installation instructions U.S. Installation Only