Raypak 1005-2005 warranty XTherm - Type H, Models, Catalog No. 2000.61C, Effective, Replaces

Models: 1005-2005

1 2
Download 2 pages 13.66 Kb
Page 2
Image 2
XTherm – Type H

XTherm – Type H

Models 1005-2005

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Primary/Secondary plumbing

CLEARANCES (in.)

 

 

 

 

 

is mandatory for proper operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front

Rear

Right

Left

Top

 

Floor

Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

Certified Minimum

24

12

1

1

0

 

0

1

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Service

24

36

24

1

10

 

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

Amp Draw**

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler †

 

Accessories †

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1005

 

12**

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1505

 

12**

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2005

 

18**

 

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

† Separate power connections are

 

 

 

 

 

 

 

 

 

 

 

 

 

factory supplied and separate supply

 

 

 

 

 

 

 

 

 

 

 

 

 

breakers must be field supplied.

 

 

 

 

 

 

 

 

 

 

 

 

 

** Current draw is for boiler only (Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

breaker must have delayed trip).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBTUH

 

 

 

 

 

Dimensions (in)

 

 

 

 

 

 

 

 

Ship

 

Model

 

 

B

 

 

 

G*

K

 

 

N

 

 

 

 

 

Weight

 

(H7-)

Input

Output

Height

D

E

F

NPT

Flue

L

M

C/A

P

R

 

Y

(Lbs.)

 

 

 

 

 

Ø

 

 

Ø

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1005

999

959

55-1/8

45

47-1/8

36-1/2

1-1/4

6

40-1/16

11-1/2

6

 

47-1/8

 

8-1/16

6-1/16

1065

 

1505

1500

1440

67-1/8

57

59-1/16

38-1/2

1-1/4

8

52-1/16

12-5/8

8

 

59-1/8

 

8-3/16

6-1/16

1234

 

2005

1999

1919

81-1/8

71

71-3/16

38-1/2

2

8

64-1/16

12-5/8

8

 

73-1/8

 

8-3/16

6-1/4

1461

 

Note: Ratings shown are for elevations up to 4,500 feet. For installations at elevations

*

For Propane Gas, all models are 1” NPT

 

above 4,500 feet, please consult the factory for additional instructions.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

Model 1005

 

 

Model 1505

 

 

 

Model 2005

 

 

Return

Supply

Minimum Pipe Size2

Supply

Minimum Pipe Size2

 

Supply

Minimum Pipe Size2

 

Temp

Temp1 (ºF)

 

 

Temp1 (ºF)

 

 

 

Temp1 (ºF)

 

 

 

(ºF)

<80’ eq

80-200’ eq

<80’ eq

80-200’ eq

 

<80’ eq

80-200’ eq

 

 

 

 

 

 

 

60

138

2” NPT

2-1/2” NPT

147

2” NPT

2-1/2” NPT

 

154

2” NPT

2-1/2” NPT

 

80

138

2” NPT

2-1/2” NPT

147

2” NPT

2-1/2” NPT

 

154

2-1/2” NPT

3” NPT

 

100

138

2-1/2” NPT

3” NPT

147

2-1/2” NPT

3” NPT

 

154

2-1/2” NPT

3” NPT

 

120

145

2-1/2” NPT

3” NPT

158

2-1/2” NPT

3” NPT

 

170

2-1/2” NPT

3” NPT

 

140

165

2-1/2” NPT

3” NPT

178

2-1/2” NPT

3” NPT

 

190

2-1/2” NPT

3” NPT

 

160

185

2-1/2” NPT

3” NPT

198

2-1/2” NPT

3” NPT

 

210

2-1/2” NPT

3” NPT

1– Approximate high fire heater outlet temperature based on the standard heater pump and recommended connecting pipe size.

2– Minimum pipe size based on total equivalent feet of supply and return piping between the system loop and heater.

Catalog No.: 2000.61C

Effective: 12-01-10