Hi Delta – Type P
Models 1802B-2342B
Model
RATE OF FLOW AND PRESSURE DROP
Model |
| Max. Flow |
|
| Min. Flow |
| ||||
|
|
|
|
|
|
|
|
|
| |
| GPM |
| ΔP (ft) |
| ΔT | GPM |
| ΔP (ft) |
| ΔT |
|
|
|
|
|
|
|
|
|
|
|
1802B | 132 |
| 18.7 |
| 23 | 102 |
| 11.2 |
| 30 |
|
|
|
|
|
|
|
|
|
|
|
2002B | 132 |
| 19.2 |
| 26 | 113 |
| 14.0 |
| 30 |
|
|
|
|
|
|
|
|
|
|
|
2072B | 132 |
| 19.2 |
| 27 | 117 |
| 15.1 |
| 30 |
|
|
|
|
|
|
|
|
|
|
|
2342B | 132 |
| 21.0 |
| 30 | 132 |
| 21.0 |
| 30 |
|
|
|
|
|
|
|
|
|
|
|
Model | MBTUH | A | K | T | W | Amp Draw |
| Pump | Shipping | |||
Input |
| Output | Width |
|
|
| Heater w/ Pump |
| Pump | HP | Weight (Lbs.) | |
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
1802B | 1800 |
| 1530 | 14 | 10 | 21 |
| 12 | 3/4 | 1350 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
2002B | 1999 |
| 1699 | 14 | 10 | 24 |
| 12 | 1 | 1450 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
2072B | 2070 |
| 1760 | 14 | 10 | 24 |
| 12 | 1 | 1450 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
2342B | 2340 |
| 1989 | 16 | 10 | 24 |
| 12 | 1520 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
Dimensions are in inches.
Ratings shown are for elevations up to 5,000 feet and for natural or propane gas.
For installation at elevations over 5,000 feet, please contact manufacturer.
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805)
Catalog No.: 6000.342B | Effective: | Replaces: |