Raytherm - Type H
Hydronic Heating Boilers
Model
MODELS H 2100 THRU 4001
| MBTUH |
| Dimensions (inches) |
| Approx. | |||
Model | Natural Gas | Width | Overall Height | Gas Conn. | Water Conn. | Flue Dia. | Shipping | |
No. | Input | Output | A | B | G | H | K | Weight (Lbs.) |
2100 | 1722 | 61.0 | * | 3** | 24 | 1400 | ||
2499 | 2049 | 70.0 | * | 3** | 26 | 1580 | ||
3000 | 2460 | 2 | 3** | 28 | 1750 | |||
3500 | 2870 | 2 | 3** | 30 | 1920 | |||
4000 | 3280 | 2 | 3** | 32 | 2100 |
NOTE: Ratings are for elevations up to 2,000 feet. For elevations over 2,000 feet, reduce ratings 4% for every 1,000 feet above sea level.
*
**4” on
BOILER RATE OF FLOW AND PRESSURE DROP
| Model | 10° ∆T | 20° ∆T | 30° ∆T | 40°∆T | ||||
| No. | GPM | ∆P FT | GPM | ∆P FT | GPM | ∆P FT | GPM | ∆P FT |
| N/A | N/A | 172 | 11.0 | 115 | 5.0 | N/A | N/A | |
N/A | N/A | N/A | N/A | 137 | 7.5 | 102 | 4.3 | ||
N/A | N/A | N/A | N/A | 164 | 11.2 | 123 | 6.5 | ||
| N/A | N/A | N/A | N/A | 191 | 16.2 | 144 | 9.3 | |
| N/A | N/A | N/A | N/A | N/A | N/A | 164 | 12.8 | |
| 344 | 14.0 | N/A | N/A | N/A | N/A | N/A | N/A | |
N/A | N/A | 205 | 5.3 | N/A | N/A | N/A | N/A | ||
N/A | N/A | 246 | 7.8 | N/A | N/A | N/A | N/A | ||
| N/A | N/A | 287 | 11.0 | 191 | 5.0 | N/A | N/A | |
| N/A | N/A | 328 | 14.8 | 219 | 6.8 | N/A | N/A |
N/A – Not Applicable
NOTES:
Values represent maximum flows and pressure drops for closed heating systems.
Maximum acceptable flow through heat exchanger tubes is 200 GPM
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805)
Catalog No.: 2000.26M | Effective: | Replaces: |