45
2. If the pressure reading differs by more than ± 0.2
in. WC, STOP – Call the factory for directions
on what to do next!
Safety Inspection
1. Check all thermostats and high limit settings.
2. During the following safety checks leave manome-
ters hooked up, check and record.
3. If other gas-fired appliances in the room are on the
same gas main, check all pressures on the MVB
with all other equipment running.
4. Check thermostats for ON-OFF operation.
5. Check high limits for ON-OFF operation.
6. While in operation, check flow switch operation.
7. Check the low gas pressure switch (if provided).
(For proper adjustment, use the attached
manometers, if available, to set pressure. The
scales on the switch are approximate only.) Low
gas pressure switch (if provided) must be set at
3.0 in. WC for natural gas and propane gas.
8. Make sure that the high gas pressure switch (op-
tional) is set to 3.0 in. WC for both natural gas and
propane gas.
Follow-Up
Safety checks must be recorded as performed.
Turn heater on. After main burner ignition:
1. Check manometer for proper readings.
2. Cycle heater several times and re-check readings.
3. Remove all manometers and replace caps and
screws.
4. Check for gas leaks one more time.
CAUTION: Special manifold and air settings may
be required.
Finishing
1. Record all data on the “Start-up Sheet” located at
the back of the Installation and Operating manual.
2. Disconnect the manometers and reconnect the
cap on the fan pressure switch tee and reinsert the
sealing screws into the bleedle valves.
3. Start-up is complete and the heater should be
operating properly.
Model No. Air Pressure
Setting (in. WC)
Setting
Tolerance
504 -2.3 ± 0.2 in. WC
754 -2.9 ± 0.2 in. WC
1104 -3.0 ± 0.2 in. WC
1504 -4.0 ± 0.2 in. WC
2004 -5.1 ± 0.2 in. WC
Table T: MVB Air Pressure Settings
Model No. Amp Draw Setting
Tolerance
504 1.9 +0.0/-0.2
754 2.9 +0.0/-0.2
1104 4.8 +0.0/-0.2
1504 8.1 +0.0/-0.2
2004 13.0 +0.0/-0.5
Table U: MVB Amp Draw (Reference Only)
Model No.
Manifold Gas Pressure Setting
High Fire Values (in. WC)
Natural Gas Propane Gas
504 -0.1 -0.1
754 -0.4 -0.1
1104 -1.0 -0.2
1504 -2.4 -0.6
2004 -2.0 -1.5
Table V: MVB Manifold Pressure Settings