Raypak 962-1826 warranty Raytherm - Type H, Hydronic Heating Boilers, Model, Optional One Pass

Models: 962-1826

1 2
Download 2 pages 10.42 Kb
Page 2
Image 2
Raytherm - Type H

Raytherm - Type H

Hydronic Heating Boilers

Model

 

32 1/2

 

 

K

 

 

OPTIONAL ONE PASS

11 1/4

 

 

H

 

 

 

 

 

15-1/4

 

 

 

7-7/8

 

 

 

 

J

 

 

B

 

 

 

H - OUTLET

OUT

IN

 

 

G

H - INLET

C

 

 

 

 

(OPPOSITE SIDE)

27 3/4

 

GAS

 

 

 

14

 

2 1/2

 

5 1/8

 

 

 

11 1/8

 

6

 

 

 

A

 

19 1/2

A/2

 

 

DRAFT HOOD

 

 

L

(OPTIONAL)

 

 

 

 

 

 

PUMP

 

 

 

(OPTIONAL)

 

 

 

14 1/2

 

 

11 3/4

ELEC.

 

 

 

CONN.

 

 

 

(J-BOX)

 

COMBUSTIBLE FLOOR SHIELD

 

 

1 1/8

(OPTIONAL)

5

 

 

 

MODELS 962 THRU 1826

 

 

 

 

 

Dimensions (Inches)

 

 

 

Approx.

 

MBTUH

 

Overall

Jacket

Gas

Water

 

Flue

 

Shipping

Model

Natural Gas

Width

Height

Height

Conn.

Conns.

 

Dia.

 

Weight

Size

Input

Output

A

B

C

G

H

J

K

L

(Lbs.)

H-962

961.7

788.6

52-3/8

76-1/8 (a)

33-1/2

1

2-1/2 (c)

23-5/8

14

28

705

H-1125

1124.7

922.0

59-1/4

78-1/8 (a)

33-1/2

1 (b)

2-1/2 (c)

23-5/8

16

32

745

H-1223

1222.5

1002.4

63-5/8

78-1/8 (a)

33-1/2

1 (b)

2-1/2 (c)

23-5/8

16

32

805

H-1336

1336.6

1096.0

68-5/8

80-1/8 (a)

33-1/2

1-1/4

2-1/2 (c)

23-5/8

18

36

875

H-1468

1467.0

1203.0

74-7/8

80-1/8 (a)

33-1/2

1-1/4

2-1/2 (c)

23-5/8

18

36

945

H-1631

1630.0

1336.6

81-1/8

83-1/8 (a)

36-1/2

1-1/4

2-1/2 (c)

23-5/8

18

36

985

H-1826

1825.6

1497.0

89-3/8

85-1/8 (a)

36-1/2

1-1/4

2-1/2 (c)

23-5/8

20

40

1035

NOTE: Ratings shown are for elevations up to 2,000 feet. For

(a) Add 1-1/8" to overall height for combustible floor shield option

 

elevations over 2,000, reduce ratings at the rate of 4% for each

(b) 1" or 1-1/4" contingent on boiler type or code requirements

 

1,000 feet above sea level.

 

 

 

 

 

 

 

(c) 3" NPT on single-pass option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(d) Propane input/output is 92% of standard values

 

 

 

 

 

 

 

 

 

 

 

BOILER RATE OF FLOW AND PRESSURE DROP

 

 

 

 

 

 

 

 

Model

 

10º ΔT

20º ΔT

 

30º ΔT

40º ΔT

Minimum Flow

 

Maximum Flow

 

 

 

 

 

ΔP

 

ΔP

 

 

ΔP

 

ΔP

 

 

ΔP

 

 

 

ΔP

 

 

 

No.

 

GPM

 

GPM

 

GPM

GPM

GPM

 

ΔT

 

GPM

ΔT

 

 

 

 

FT

FT

 

FT

FT

 

FT

 

FT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H-962

 

 

 

 

 

80

8.8

 

53

3.8

40

2.2

 

40

 

2.2

38

 

90

11.0

18

 

 

H-1125

 

 

 

 

 

90

12.0

 

61

5.5

47

3.3

 

45

 

3.1

40

 

90

12.0

21

TWO-

 

H-1223

 

 

 

 

 

 

 

 

76

7.0

51

4.0

 

51

 

4.0

40

 

90

12.5

22

 

H-1336

 

 

 

 

 

 

 

 

73

8.6

55

4.9

 

55

 

4.9

40

 

90

13.2

25

PASS

 

 

Exceeds Maximum Flow

 

 

 

 

 

H-1468

 

 

80

11.0

61

6.4

 

61

 

6.4

40

 

90

14.0

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H-1631

 

 

 

 

 

 

 

 

90

14.8

68

8.3

 

68

 

8.3

40

 

90

8.3

30

 

 

H-1826

 

 

 

 

 

 

 

 

 

 

 

76

10.8

 

76

 

10.8

40

 

90

15.4

34

 

 

H-962

157

 

6.1

 

 

 

 

 

 

 

 

 

 

90

 

2.1

18

 

200

9.7

8

 

 

H-1125

184

 

8.8

 

92

2.3

 

 

 

 

 

 

 

90

 

2.3

20

 

200

10.3

9

ONE-

 

H-1223

200

 

11.0

 

100

2.9

 

 

Less than Minimum Flow

 

90

 

2.4

22

 

200

11.0

10

PASS

 

H-1336

 

 

 

 

 

110

3.7

 

 

 

 

 

 

 

90

 

2.5

24

 

200

11.7

11

 

H-1468

 

 

 

 

 

120

4.5

 

 

 

 

 

 

 

90

 

2.7

27

 

200

12.2

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H-1631

 

 

 

 

 

134

6.0

 

 

 

 

 

 

 

90

 

2.8

30

 

200

13.0

13

 

 

H-1826

 

 

 

 

 

150

8.0

 

100

3.7

 

 

 

90

 

3.0

33

 

200

14.7

15

NOTES:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Values represent maximum flows and pressure drops for closed heating systems

Maximum acceptable flow through heat exchanger tubes is 90 GPM (two-pass); 200 GPM (one-pass)

Single-pass heat exchangers are to be used only when flow rates exceed the allowable for two-pass

Raypak, Inc. ƒ 2151 Eastman Avenue, Oxnard, CA 93030 ƒ (805) 278-5300 ƒ Fax (800) 872-9725 ƒ www.raypak.com

Catalog No.: 2000.24O

Effective: 04-15-10

Replaces: 12-01-07

Page 2
Image 2
Raypak 962-1826 warranty Raytherm - Type H, Hydronic Heating Boilers, Model, Optional One Pass