Raypak Rate Of Flow And Pressure Drop, Hi Delta - Type P, Models 992B-1532B, Max. Flow, ΔP ft

Models: 992B-1532B

1 2
Download 2 pages 42.98 Kb
Page 2
Image 2
Hi Delta – Type P

Hi Delta – Type P

Models 992B-1532B

Model

RATE OF FLOW AND PRESSURE DROP

Model

 

Max. Flow

 

 

Min. Flow

 

 

GPM

 

ΔP (ft)

 

ΔT

GPM

 

ΔP (ft)

 

ΔT

992B

132

 

14.0

 

13

56

 

2.5

 

30

 

 

 

 

 

 

 

 

 

 

 

1262B

132

 

15.5

 

16

71

 

4.5

 

30

 

 

 

 

 

 

 

 

 

 

 

1532B

132

 

16.5

 

20

87

 

7.2

 

30

 

 

 

 

 

 

 

 

 

 

 

Model

MBTUH

A

K

T

W

Amp Draw

Shipping
Input

 

Output

Width

 

 

 

(w/ Pump)

Weight (Lbs.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

992B

990

 

842

57-1/8

10

10

16-13/16

21.0

900

 

 

 

 

 

 

 

 

 

 

1262B

1260

 

1071

68-1/2

12

10

20-9/16

21.0

1010

 

 

 

 

 

 

 

 

 

 

1532B

1530

1301

79-7/8

12

10

24-3/8

21.0

1225

 

 

 

 

 

 

 

 

 

 

Dimensions are in inches.

Ratings shown are for elevations up to 5,000 feet and for natural or propane gas.

For installation at elevations over 5,000 feet, please contact manufacturer.

Raypak, Inc. ￿ 2151 Eastman Avenue, Oxnard, CA 93030 ￿ (805) 278-5300 ￿ Fax (800) 872-9725 ￿ www.raypak.com

Catalog No.: 6000.332B

Effective: 8-15-08

Replaces: 3-1-07