Models with Motorized Modulation: H2, H6, W2

Sizes 2100-4001 are equipped with a single motorized modulating valve controlled by a temperature controller that offers full modulation down to 20% of rated input BTU.

HIGH LIMIT AND

TEMP CONTROL

TEMP CONTROL

FOR MOTORIZED MODULATION

LIMIT CONTROLS

1. HIGH LIMIT

If boiler is equipped with a manual reset High Limit, push the reset button and set the Limit(s) to 30° - 40°F above operating temperature.

2.FLOW SWITCH

Dual purpose control shuts off boiler in case of

pump failure or low water condition.

3. 100% PILOT SAFETY

All standard boilers above 400,000 BTUH input are equipped with pilot safety(ies), which close the main valve within 8/10 of a second whenever the pilot flame is interrupted. Pilot flame is automatically lit when the device is powered. Unit performs its own safety check and opens the main valve only after the pilot is proven to be lit.

4. LOW WATER CUTOFF

The low water cut off automatically shuts down burner whenever water level drops below probe. 90 second time delay prevents premature lockout due to temporary conditions such as power failure or air pock-

ets.

12

5. HIGH AND LOW GAS PRESSURE SWITCHES These switches sense either high or low gas pres- sures and automatically shut down burners if abnormal

pressures exist.

6.BLOCKED VENT SHUT-OFF SYSTEM

All indoor boilers below 300,000 BTUH input em-

ploy a blocked vent shut-off system designed to shut off main burner gas in the event the venting system is totally blocked.

In the event the blocked vent shut-off system is actuated, do not attempt to place the boiler in operation, but contact a qualified service agency.

7.FLAME ROLL-OUT

SAFETY SHUT-OFF SYSTEM

All boilers below 300,000 BTUH input employ a flame roll-out safety shut-off system designed to shut- off the main burner gas in the event of sustained flame roll-out.

In the event the flame roll-out safety system is actuated, do not attempt to place the boiler in operation, but contact a qualified service agency

3

4

5

MANUAL RESET

FLOW SWITCH

PILOT SAFETY

LOW WATER

HIGH OR LOW GAS

HI LIMIT

Fig # 9314

Fig # 9317

CUTOFF

PRESSURE SWITCH

Fig # 8929

Fig # 9316

Fig # 9312