Raypak HD101 Suggested Minimum Maintenance Schedule, Yearly Beginning of each heating season

Models: HD101 HD401

1 8
Download 8 pages 40.56 Kb
Page 5
Image 5
MAINTENANCE

MAINTENANCE

Suggested Minimum

Maintenance Schedule:

Regular service by a qualified service agency and maintenance must be performed to ensure maximum heater operating efficiency. Maintenance as outlined below may be performed by the owner.

Yearly (Beginning of each heating season):

1.Annual service call by qualified service agency.

2.Visually check top of vent for soot. Call service person to clean. Some sediment at bottom of vent is normal.

3.Visually inspect venting system for proper func- tion, deterioration or leakage.

4.Check that heater area is free from combustible materials, gasoline, and other flammable vapors and liquids.

5.Check for and remove any obstruction to the flow of combustion or ventilation air to heater.

6.Follow pre-start-up check in the Initial Start-up section.

7.Visually inspect burner flame. Should see light blue flame. Visually inspect hot surface igniter for damage, cracking or debris build-up.

8.Check operation of safety devices. Refer to manu- facturer’s instructions.

9.Follow oil-lubricating instructions on circulator (if required). Over-oiling will damage circulator. Water-lubricated circulators do not need oiling.

10.To avoid potential of severe burn, DO NOT REST HANDS ON OR GRASP PIPES. Use a light touch - return piping will heat up quickly.

11.Check blower and blower motor. Clean and oil as necessary.

12.Check for piping leaks around circulators, relief valves and other fittings. Repair, if found. DO NOT use petroleum based stop leak.

13. Check air filter and replace if necessary.

Daily:

1.Check that heater area is free from combustible materials, gasoline, and other flammable vapors and liquids.

2.Check for and remove any obstruction to the flow of combustion or ventilation air to heater.

Monthly:

1.Check for piping leaks around circulators, mixing valves, relief valves, and other fittings. If found, repair at once. DO NOT use petroleum-based stop leak compounds.

2.Visually inspect burner flame.

3.Visually inspect venting system for proper func- tion, deterioration or leakage.

4.Check air vents for leakage.

Quarterly:

1.Check relief valve. Refer to manufacturer’s instructions on valve.

2.Test low water cut-off, if used. Refer to manufac- turer’s instructions.

3.Check the air filter; replace if necessary.

5

Page 5
Image 5
Raypak HD101, HD401 Suggested Minimum Maintenance Schedule, Yearly Beginning of each heating season, Daily, Monthly