Raypak HD101, HD401 dimensions DIVISION 23 52 FINNED WATER-TUBEBOILERS, PART 1 - GENERAL

Models: HD101 HD401

1 4
Download 4 pages 39.79 Kb
Page 1
Image 1
DIVISION 23 52 33.13

Hi Delta SS™, TYPE H - MODELS HD101-HD401

Catalog No.:

2000.961

Effective:

6-25-09

SUGGESTED SPECIFICATIONS

Replaces:

New

 

 

 

 

DIVISION 23 52 33.13

FINNED WATER-TUBE BOILERS

PART 1 - GENERAL

1.1SUMMARY

A.Section includes gas-fired, copper finned-tube hydronic heating boilers

B.Related Sections

Specifier Note: Use as needed

1.Building Services Piping – Division 23 21 00

2.Breeching, Chimneys, and Stacks (Venting) – Division 23 51 00

3.HVAC Instrumentation and Controls – Division 23 09 00

4.Electrical – Division 23 09 33

1.2REFERENCES

A.ANSI Z21.13/CSA 4.9

B.ASME, Section IV

C.2006 UMC, Section 1107.6

D.ANSI/ASHRAE 15-1994, Section 8.13.6

E.National Fuel Gas Code, ANSI Z223.1/NFPA 54

F.I=B=R

G.NEC

1.3SUBMITTALS

A.Product data sheet (including dimensions, rated capacities, shipping weights, accessories)

B.Wiring diagram

C.Warranty information

D.Installation and operating instructions

1.4QUALITY ASSURANCE

A.Regulatory Requirements

1.ANSI Z21.13/CSA 4.9

2.Local and national air quality regulations for low NOx (<20 PPM NOx emissions) boilers

B.Certifications

1.CSA

2.ASME H Stamp and National Board Listed

3.ISO 9001

1.5WARRANTY

A.Limited one-year warranty from date of installation

B.Limited twenty-year thermal shock warranty

C.Limited ten-year closed-system heat exchanger warranty

PART 2 - PRODUCTS

2.1MANUFACTURER A. Raypak, Inc.

1.Contact: 2151 Eastman Ave., Oxnard, CA 93030; Telephone: (805) 278-5300;

Fax: (800) 872-9725; Web site: www.raypak.com

Project Name / Date

Division 23 52 33.13 - 1

Page 1
Image 1
Raypak HD101, HD401 dimensions DIVISION 23 52 FINNED WATER-TUBEBOILERS, PART 1 - GENERAL, Specifier Note Use as needed