2. Product: Hi Delta SS™ copper
2.2BOILERS A. General
1. The boiler(s) shall be fired with |
| gas at a rated input of |
| BTU/hr. |
2.The boiler(s) shall be CSA tested and certified with a minimum thermal efficiency of 84 percent at full fire.
3.The boiler(s) shall be ASME inspected and stamped and National Board registered for 160 PSIG working pressure, complete with a Manufacturer's Data Report.
4.The boiler(s) shall have a floor loading of 45 lbs. /square foot or less.
B.Heat Exchanger
1.The heat exchanger shall be of a
2.The heat exchanger shall be sealed to 160 PSIG rated cast iron headers with high temperature silicone "O" ring gaskets.
3.The low water volume heat exchanger shall be
4.The headers shall be secured to the tube sheet by stud bolts with flange nuts to permit inspection and maintenance without removal of external piping connections.
5.The boiler(s) shall be capable of operating at inlet water temperatures as low as 105°F without condensation.
C.Burners
1.The tubular burners shall have gas orifices, punched ports and slots, be capable of quiet ignition and extinction without flashback at the orifice, and be manufactured from corrosion- resistant, stainless steel with low expansion coefficient.
2.The burners will be supplied with a
D.Pilot Control System
1.The boiler(s) shall be equipped with a 100 percent safety shutdown system.
2.The ignition shall be Hot Surface Ignition type with full flame rectification by remote sensing separate from the ignition source, with a three
3.The igniter will be located away from the water inlet to protect the device from condensation during startup.
4.An external viewing port shall be provided, permitting visual observation of burner operation.
E.Gas Train
1.The boiler(s) shall have
2.Gas control trains shall have a redundant safety
F.Boiler Control
1.The following safety controls shall be provided:
a.High limit control
b.Flow switch
c.PSIG ASME pressure relief valve, piped by the installer to an approved drain
d.Temperature and pressure gauge
2.The boiler(s) shall be equipped with an
G.Firing Mode
1.For models HD101 – HD401, provide
H.Boiler Diagnostics
Project Name / Date | Division 23 52 33.13 - 2 |