T-2 Metasys Interface
Interface Board
Certified Metasys Compatibility ProSoft Series 1500 Translator
9600 Baud Transfer Rate
Read/Write Attributes
Analog/Binary
Total B6000 BMS Program Access
Data Integrity Protocol
Summation/Modulus Error Checking
Auto Command Error Feedback
LED Diagnostic Indicators
Port 1 | Port 2 |
Green - Active | Green - Active |
Red - Error | Red - Error |
Sample Specification
Section I: General Requirements
Electrical Characteristics
120 VAC, 0.25A, 60 Hz
Ambient Conditions
Temperature:
Humidity: 90% RH
Enclosure
Heavy Gauge Steel Lockable Access Door Tamper Resistant Design
15 3/16” L x 8” W x 4 3/4” D Boiler or Remote Mounted
Limited One-Year Warranty
U® L
1.Provide a Raypak
2.The interface shall be microprocessor based.
3.The interface shall be UL Listed.
4.The interface shall carry a
5.The interface and boiler control system shall be manufactured by the same company and shall carry single source accountability.
Section II: Equipment Enclosure
1.The interface enclosure shall be constructed of heavy gauge steel and shall be protected with a
2.The front access door of the interface enclosure shall be lockable and the enclosure shall be tamper resistant.
Section III: Control Functions
1.The interface shall provide seamless communications integration between the Raypak B6000
2.The interface shall utilize summation/modulus error checking and auto command error feedback to ensure data integrity.
3.The interface shall allow analog and binary
a)Reset parameters including: Setpoint, Reset Ratio, Temperature Rise and Control Band.
b)Outdoor cutoff parameters including: Outdoor Cutoff Temperature and Outdoor Cutoff Deadband.
c)Secondary operating parameters including: Firing Step Increment, Pump
d)Setback parameters including: Setback Period Scheduling and Setback Activation.
e)
Section IV: Display Functions
1.The interface shall have port active and error diagnostic lights for both interface ports.
2.The interface shall allow analog and binary
a)Current temperatures including: Water Temperature, Outdoor Air Temperature, and Target Temperature.
b)Boiler operating status including: Valve Position, and Current Firing Rate.
c)Fault indication including: Low Water, Low Gas Pressure, High Gas Pressure, High Temp, Low Water Pressure, Low Flow, No Pilot and Manual Override Status.
d)Secondary operating parameters including: Time Remaining Till Lead Boiler Rotation and Valve Operating Times.