Rheem Advantage Plus Rheem-Ruud AdvantagePlus, Recovery Capacities, Clearances To Combustibles

Models: Advantage Plus

1 4
Download 4 pages 2 Kb
Page 3
Image 3
Rheem-Ruud AdvantagePlus

Rheem-Ruud AdvantagePlus

RECOVERY CAPACITIES

MODEL

 

 

 

 

 

 

TEMPERATURE RISE - DEGREES F - GALLONS PER HOUR

 

 

 

NUMBER
CAPACITY

INPUT

EFFICIENCY

40°

50°

60°

70°

80°

90°

100°

110°

120°

130°

140°

HE45-100

45

100,000

95%

288

230

192

165

144

128

115

105

96

N/A

N/A

HE45-130

45

130,000

95%

374

299

249

214

187

166

150

136

125

N/A

N/A

HE80-130

80

130,000

95%

374

299

249

214

187

166

150

136

125

N/A

N/A

HE119-130

119

130,000

95%

374

299

249

214

187

166

150

136

125

N/A

N/A

HE45-160

45

160,000

95%

461

368

307

263

230

205

184

167

154

142

132

HE80-160

80

160,000

95%

461

368

307

263

230

205

184

167

154

N/A

N/A

HE119-160

119

160,000

95%

461

368

307

263

230

205

184

167

154

N/A

N/A

HE45-199

45

199,000

95%

573

458

382

327

286

255

229

208

191

176

164

HE80-199

80

199,000

95%

575

460

384

329

288

256

230

209

192

N/A

N/A

HE119-199

119

199,000

95%

575

460

384

329

288

256

230

209

192

N/A

N/A

Recovery rating is based on a recovery efficiency obtained in an UL laboratory.

This model exceeds the minimum NAECA energy factor requirements of ASHRAE 90.1b-1992.

MAXIMUM DELIVERY (in gallons) (Includes useable storage and recovery for indicated times)

MODEL

 

 

 

 

TEMP.

5

10

15

20

30

45

1

2

3

MIN. TO RECOVER

NUMBER

CAPACITY

INPUT

EFFICIENCY

RISE

MIN.

MIN.

MIN.

MIN.

MIN.

MIN.

HR.

HR.

HR.

CONTENTS

HE45-100

45

100,000

 

95%

100°

41

51

60

70

89

118

147

262

377

23

HE45-130

45

130,000

 

95%

100°

44

56

69

81

106

144

181

331

481

18

HE80-130

80

130,000

 

95%

100°

68

81

93

106

131

168

206

355

505

32

HE119-130

119

130,000

 

95%

100°

96

109

121

134

159

196

234

383

533

48

HE45-160

45

160,000

 

95%

100°

47

62

78

93

124

170

216

400

584

15

HE80-160

80

160,000

 

95%

100°

71

87

102

117

148

194

240

424

609

26

HE119-160

119

160,000

 

95%

100°

99

115

130

145

176

222

268

452

637

39

HE45-199

45

199,000

 

95%

100°

51

70

89

108

146

203

261

490

719

12

HE80-199

80

199,000

 

95%

100°

75

94

114

133

171

229

286

516

747

21

HE119-199

119

199,000

 

95%

100°

103

122

141

161

199

257

314

544

774

31

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIMENSIONAL INFORMATION (All dimensions shown in inches)

 

 

 

 

 

 

 

 

 

 

MODEL

 

 

 

 

 

 

APPROX. SHIPPING

 

 

 

 

 

 

 

NUMBER

HEIGHT

WIDTH

DEPTH

VENT

 

WEIGHT (LBS.)

 

 

 

 

 

 

 

 

HE45-100

42

23-1/2

32

2

 

 

175

 

 

 

 

 

 

 

 

HE45-130

42

23-1/2

32

2

 

 

175

 

 

 

 

 

 

 

 

HE45-160

42

23-1/2

32

3

 

 

175

 

 

 

 

 

 

 

 

HE45-199

42

23-1/2

32

3

 

 

175

 

 

 

 

 

 

 

 

HE80-130

72

23-1/2

32

2

 

 

235

 

 

 

 

 

 

 

 

HE80-160

72

23-1/2

32

3

 

 

235

 

 

 

 

 

 

 

 

HE80-199

72

23-1/2

32

3

 

 

235

 

 

 

 

 

 

 

 

HE119-130

73

 

27

36

2

 

 

405

 

 

 

 

 

 

 

 

HE119-160

73

 

27

36

3

 

 

405

 

 

 

 

 

 

 

 

HE119-199

73

 

27

36

3

 

 

405

 

 

 

 

 

 

 

 

Models with inputs of 100,000 kBtu and 130,000 kBtu are certified to vent with 2” Schedule 40 PVC, CPVC or ABS pipe.

CLEARANCES TO COMBUSTIBLES

MODEL

REAR /

 

 

NUMBER

SIDES

FRONT*

TOP

HE45-100

0

0

0

HE45-130

0

0

0

HE45-160

0

0

0

HE45-199

0

0

0

HE80-130

0

0

0

HE80-160

0

0

0

HE80-199

0

0

0

HE119-130

0

0

0

HE119-160

0

0

0

HE119-199

0

0

0

* 24" service clearance recommended

Commercial water heaters

from Rheem-Ruud
Page 3
Image 3
Rheem Advantage Plus Rheem-Ruud AdvantagePlus, Recovery Capacities, Clearances To Combustibles, Commercial water heaters