14.6 Flue Blower Vertical Installation

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

14.6 Flue Blower Vertical Installation

 

Intake &

 

Exhaust

 

Covers

 

Mounting Plate

 

to Vent Box

 

fixing screws

Air Intake

Gaskets

Adaptor

 

 

Vent Box

 

Mounting Plate

 

to Flue Blower

 

screws

Intake &

Air Intake Adapter

 

Exhaust

 

Covers

 

 

Gasket

 

Flexible Air

 

Duct

Mounting Plate

to Vent Box

fixing screws

NOTE: Seperated combustion model shown.

To remove the blower, remove screws securing the fan and mounting plate to the vent box.

To remove the blower from the mounting plate, remove screws.

Refit in reverse order.

To change the vent and air intake orientation from back to top, remove the blower and mounting plate as above.

Remove intake (if applicable) and exhaust covers from top of the heater.

Rotate the blower, mounting plate and gasket clockwise until the flue adapter lines up with the top hole. Secure screws.

If applicable, remove the flexible air duct from the air intake adapter on the back.

If applicable, remove the air intake adapter from the back of the heater and install in the appropriate hole on top. Reconnect the flexible air duct.

Install intake and exhaust covers over the back holes.

MODEL

Flue Blower P/N

UHA[X][S] 30 -75

UHA[X][S] 100 - 125

90710404

90710405

 

 

IT IS IMPORTANT THAT ONLY THE CORRECT FLUE BLOWER SPECIFIED FOR EACH MODEL TYPE IS USED WHEN REPLACING THESE ITEMS.

Carry out a start-up after working on or changing an flue blower. See Page 33, Section 11.